10 Technical data
Maschinenfabrik Reinhausen GmbH 2016
215
5163667/00 EN
TRAFOGUARD® ISM®
Standards and directives
Electrical safety
IEC
61010-1
IEC 61010-2-030
Safety requirements for electrical measurement
and control and regulation equipment and labora-
tory instruments
▪
Protection class 1
▪
Overvoltage category III
▪
Contamination level 2
IEC 60950-1
Information technology equipment – Safety
Table 71: Electrical safety
Electromagnetic compatibility
Immunity from electrostatic discharge (ESD)
▪
Front panel and operating elements
–
Contact: ±8 kV
–
Air: ±15 kV
▪
Terminals, plug connectors, and interfaces:
–
Contact: ±6 kV
–
Air: ±8 kV
IEC 61000-4-3
Immunity from high-frequency electromagnetic
fields
▪
20 V/m; 80...4000 MHz; 80% AM
▪
20 V/m; 900 MHz ±5 MHz; PM
IEC 61000-4-4
Immunity from quick, transient electrical disturban-
ces (burst)
▪
Power supply: 4 kV
▪
Measurement (UI1/3): 4 kV
▪
Digital I/O: 4 kV
▪
Analog I/O, shielding on both sides: 4 kV
▪
Communication interfaces, shielding on both
sides: 4 kV
IEC 61000-4-5
Immunity from surges
▪
AC power supply: 4 kV CM, 2 kV DM
▪
DC power supply: 2 kV CM, 1 kV DM
▪
Measurement (UI1/3): 4 kV CM, 2 kV DM
▪
Digital I/O: 2 kV CM, 1 kV DM
▪
Analog I/O, shielding on both sides: 2 kV CM
▪
Communication interfaces, shielding on both
sides: 2 kV CM
10.9
Summary of Contents for TRAFOGUARD ISM