4 Mounting
Maschinenfabrik Reinhausen GmbH 2016
42
5163667/00 EN
TRAFOGUARD® ISM®
Cable
Assembly
Cable type
Conductor cross-
section
Max. length
CAN bus
CPU I
Shielded
0.75 mm²
2,000 m (total CAN
bus)
Ethernet RJ45
CPU I
min. Cat-5,
shielded S/FTP
-
100 m
Ethernet FO
MC 2-2, SW
3-3
Duplex LC
Multimode, OM3,
1,310 nm
-
2000 m
Table 6: Recommendation for connection cable
*) Observe line capacitance, see note above.
Information about connecting serial interfaces RS232 and RS485
NOTICE
Damage to the device
Using the wrong data cable may damage the device.
► Only use data cables which comply with the description below.
RS232 (D-SUB 9-pole)
For connecting the device via the RS232 interface (COM2), use a data cable
with the following structure:
Figure 29: RS232 data cable (9-pole)