6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
121
5163667/00 EN
TRAFOGUARD® ISM®
Setting the hysteresis
To set the hysteresis, proceed as follows:
1.
Go to
Settings > Parameters > Bandwidth monitoring > Hysteresis
.
2.
Enter hysteresis.
3.
Press the
Accept
button to save the modified parameter.
Setting the delay time
To set the delay time, proceed as follows:
1.
Go to
Settings > Parameters > Bandwidth monitoring > Delay time
.
2.
Enter delay time.
3.
Press the
Accept
button to save the modified parameter.
Also refer to
2
2
Temperature monitoring
You can set different limit values for every measured/calculated tempera-
ture. If the measured temperature is greater than limit value > or >>, the de-
vice triggers an event message. If the measured temperature is less than
limit value < or <<, the device triggers an event message.
Figure 87: Temperature monitoring
To set the temperature monitoring, proceed as follows:
1.
Go to
Settings > Parameters > Temperature monitoring
.
2.
Select the parameter you want.
3.
Set the parameter you want.
4.
Press the
Accept
button to save the modified parameter.
6.7.5