6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
127
5163667/00 EN
TRAFOGUARD® ISM®
Cooling stage
Meaning
S2
Operation with cooling stage 2
S3
Operation with cooling stage 3
S4
Operation with cooling stage 4
S5
Operation with cooling stage 5
S6
Operation with cooling stage 6
Configuring cooling stages
To control the cooling system you have to set the following parameters for
every cooling stage:
▪
Operating duration
▪
Number of starts
▪
Activate cooling stage
▪
Switch on input variable
▪
Switch off input variable
▪
Switching point
▪
Hysteresis
▪
Switch-on delay
▪
Alternating mode
▪
Periodic mode
▪
Active if error
Figure 92: Configure cooling stage
Operating duration
The device records the operating duration of the cooling stage. You can use
this parameter to reset the operating duration of the relevant cooling stage if
you have replaced fans or pumps on the cooling system, for example.