4 Mounting
Maschinenfabrik Reinhausen GmbH 2016
31
5163667/00 EN
TRAFOGUARD® ISM®
Wiring requirement of installation site
Note the following when selecting the installation site:
▪
The system's overvoltage protection must be effective.
▪
The system's ground connection must comply with all technical regula-
tions.
▪
Separate system parts must be joined by a potential equalization.
▪
The device and its wiring must be at least 10 m away from circuit-break-
ers, load disconnectors and busbars.
Wiring requirement of operating site
Note the following when wiring the operating site:
▪
Route the connecting leads in grounded metal cable ducts.
▪
Do not route lines which cause interference (for example power lines)
and lines susceptible to interference (for example signal lines) in the
same cable duct.
▪
Maintain a space of more than 100 mm between lines which cause in-
terference and those which are susceptible to interference.
Figure 15: Recommended wiring
1
Cable duct for lines causing
interference
3
Cable duct for lines suscepti-
ble to interference
2
Line causing interference (e.g.
power line)
4
Line susceptible to interfer-
ence (e.g. signal line)
▪
Short-circuit and ground reserve lines.
▪
Never connect the device with a collective line containing numerous
wires.
▪
To transmit signals, use shielded lines with individual conductors (outgo-
ing conductor/return conductor) twisted in pairs.
▪
Connect full surface of shielding (360º) to device or to a nearby ground-
ing bar.
4.2.1
4.2.2