6 Commissioning
Maschinenfabrik Reinhausen GmbH 2020
114
4983703/01 EN
VACUTAP
®
VV-Ex
6.1.1.2 Bleeding suction pipe on pipe connection S
1. Remove screw cap from pipe connection S.
Figure 105: Pipe connection S
2. Open vent screw and bleed piping.
3. Close vent screw.
4. Seal vent screw with screw cap.
6.1.2 Grounding the on-load tap-changer
If necessary, reduce the stated tightening torque according to the grounding
line used.
1. Ground the on-load tap-changer. To do this, only connect the grounding
terminal on the on-load tap-changer head with the transformer cover.
Figure 106: Grounding terminal on on-load tap-changer head