7 Fault elimination
Maschinenfabrik Reinhausen GmbH 2020
126
4983703/01 EN
VACUTAP
®
VV-Ex
7 Fault elimination
WARNING
Danger of explosion!
Danger of death from explosive gases under the on-load tap-changer head
cover!
► Ensure that there are no open flames, hot surfaces or sparks (for exam-
ple caused by static charging) in the immediate surroundings and that
none arise.
► De-energize all auxiliary circuits (for example tap-change supervisory de-
vice) before removing the on-load tap-changer head cover.
► Do not operate any electrical devices during the work (for example risk of
sparks caused by impact wrench).
► Only use conductive and grounded hoses, pipes, and pump equipment
that are approved for flammable liquids.
NOTICE
Damage to the on-load tap-changer and transformer!
If the protective relay or other protective devices trip, this can indicate dam-
age to the on-load tap-changer and transformer. The transformer must not
be energized without being inspected first.
► Check on-load tap-changer and transformer when protective relay or
other protective devices have been tripped.
► Do not use the equipment again until you are sure there is no damage to
the on-load tap-changer or transformer.
NOTICE
Damage to motor-drive unit!
Damage to the motor-drive unit due to condensate in protective housing of
motor-drive unit.
► Always keep protective housing of the motor-drive unit tightly closed.
► In the event of operation interruptions of more than 2 weeks, connect and
operate the anti-condensation heater in the motor-drive unit. If this is not
possible, e.g. during transportation, place a sufficient amount of desiccant
in the protective housing.
The table below is intended to assist with detecting and, where possible,
remedying faults.
For more information, please consult the operating instructions for the pro-
tective relay or the relevant protective device.
In the event of faults on the on-load tap-changer and motor-drive unit which
cannot be easily corrected on site, or if the protective relay or additional pro-
tective devices have been tripped, please inform your authorized MR repre-
sentative, the transformer manufacturer or contact MR directly.
Maschinenfabrik Reinhausen GmbH
Technical Service
Postfach 12 03 60