5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
49
4983703/01 EN
VACUTAP
®
VV-Ex
5. Place on-load tap-changer head cover on on-load tap-changer head and
secure.
Figure 27: On-load tap-changer head cover
5.3.2 Connecting the tap winding and on-load tap-changer take-off
lead
NOTICE
Damage to the on-load tap-changer!
Connecting leads which place mechanical strain on the on-load tap-changer
will damage the on-load tap-changer!
► Establish and secure connections with care.
► Do not twist connection contacts.
► Connect connecting leads without warping or deforming.
► If necessary use an expansion loop for connecting leads.
1. Connect tap winding and on-load tap-changer take-off lead in accordance
with the connection diagram included with the delivery.
2. If connection leads have to cross the open surface of the oil compartment/
change-over selector, there must be a clearance of 50 mm between the
connecting leads and the surface of the oil compartment/change-over se-
lector.
The designations of the on-load tap-changer's connection contacts are
shown in the connection diagram. The connection contacts are provided with
vertical through-holes (11 mm diameter for M10 screws, see appendix
[