5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
60
4983703/01 EN
VACUTAP
®
VV-Ex
5.4.2 Connecting the tap winding and on-load tap-changer take-off
lead
NOTICE
Damage to the on-load tap-changer!
Connecting leads which place mechanical strain on the on-load tap-changer
will damage the on-load tap-changer!
► Establish and secure connections with care.
► Do not twist connection contacts.
► Connect connecting leads without warping or deforming.
► If necessary use an expansion loop for connecting leads.
1. Connect tap winding and on-load tap-changer take-off lead in accordance
with the connection diagram included with the delivery.
2. If connection leads have to cross the open surface of the oil compartment/
change-over selector, there must be a clearance of 50 mm between the
connecting leads and the surface of the oil compartment/change-over se-
lector.
The designations of the on-load tap-changer's connection contacts are
shown in the connection diagram. The connection contacts are provided with
vertical through-holes (11 mm diameter for M10 screws, see appendix
[
5.4.3 Performing transformer ratio test before drying
NOTICE
Damage to the on-load tap-changer!
Damage to the on-load tap-changer due to transformer ratio test being in-
correctly performed.
► Do not perform more than 250 tap-change operations on the on-load tap-
changer. If more than 250 tap-change operations are to be performed,
completely fill the oil compartment with insulating fluid and lubricate slid-
ing surfaces of contacts on the selector and selector gear with insulating
fluid.
► Only switch the on-load tap-changer from one operating position to the
next via the upper gear unit. You can use a short tube (diameter 25 mm)
with screwed-in coupling bolt (diameter 12 mm) with a hand wheel or
crank for this, for example. When using a drill, do not exceed a maximum
speed of 250 rpm.
► Always check the operating position reached through the inspection win-
dow in the on-load tap-changer head cover. Never overshoot the end po-
sitions, which are indicated in the connection diagram supplied with the
delivery.
► For multiple-column applications with a shared drive, link all on-load tap-
changer heads to one another using the horizontal drive shaft parts.