5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
85
4983703/01 EN
VACUTAP
®
VV-Ex
When making the electrical connection for the protective relay, proceed as
follows.
1. Connect protective conductor with cable cross-section of 1…4 mm
2
to
cylinder head screw.
2. Take off MR dummy plug.
Figure 66: Dummy plug
3. Insert explosion-certified cable bushing into tapped hole on side of termi-
nal box.
4. Loosen the three screws on the terminal box cover and lift off the terminal
box cover.
Figure 67: Terminal box cover