Recirculating cooler
(
Chiller
)
30
First PID
1_PI
Normal temperature (5
~
35
℃
) PID integral item
0
~
9999S (0 no
action)
120
First PID
1_PD
Normal temperature (5
~
35
℃
) PID differential
term
0
~
9999S (0 no
action)
30
First PID
1_PM
Normal temperature (5
~
35
℃
) PID temperature
0--Cooling
1-- Heating
0
First PID
1_PT
Normal temperature (5
~
35
℃
) PID control period
1
~
199S
20
First PID
1_PO
Normal temperature (5
~
35
℃
) PID overshoot
suppression
0~9.99
℃
1
First PID
1_PC
Normal temperature (5
~
35
℃
) PID small signal
cut off
0
~
10.0%
1
Second PID
2_PP
Low temperature (<5
℃
)
PID proportional item
0.1
~
999.9%
5
Second PID
2_PI
Low temperature (<5
℃
)
PID integral item
0
~
9999S (0 no
action)
120
Second PID
2_PD
Low temperature (<5
℃
)
PID differential term
0
~
9999S (0 no
action)
30
Second PID
2_PM
Low temperature (<5
℃
)
PID temperature control
mode
2--Cooling
3-- Heating
0
Second PID
2_PT
Low temperature (<5
℃
)
PID control period
1
~
199S
20
Second PID
2_PO
Low temperature (<5
℃
)
PID overshoot
suppression
0~9.99
℃
1
Second PID
2_PC
Low temperature (<5
℃
)
PID small signal cut off 0
~
10.0%
1
Third PID
3_PP
High temperature (>35
℃
)
PID proportional item
0.1
~
999.9%
5
Third PID
3_PI
High temperature (>35
℃
)
PID integral item
0
~
9999S (0 no
action)
120
Third PID
3_PD
High temperature (>35
℃
)
PID differential term
0
~
9999S (0 no
action)
30