Recirculating cooler
(
Chiller
)
31
Third PID
3_PM
High temperature (>35
℃
)
PID temperature control
mode
4--Cooling
5-- Heating
0
Third PID
3_PT
High temperature (>35
℃
)
PID control period
1
~
199S
20
Third PID
3_PO
High temperature (>35
℃
)
PID overshoot
suppression
0~9.99
℃
1
Third PID
3_PC
High temperature (>35
℃
)
PID small signal cut off 0
~
10.0%
1
Alarm parameter database: password 0055. Long press
【
menu
】
key to enter
with code;
Item
Parameter
Meaning
Option or
Range
Initial Data
High
temperatu re
alarm 1
E_H1
The first point of the user
defined high temperature
alarm
C_PL+1 - C_PH
C_PH
High
temperatu re
alarm 2
E_H2
The second point of the
user defined high
temperature alarm
E_H1+1 ~C_PH
C_PH
Low
temperatu re
alarm 1
E_L1
The first point of the user
defined low temperature
alarm
C_PL-C_PH-1
C_PL
Low
temperatu re
alarm 2
E_L2
The second point of the
user defined low
temperature alarm
C_PL~E_L1
C_PL
Water level
enable
E_LW
Set water level switch to
enable
0 - No alarm 1 -
alarm
1
Water flow
enable
E_LF
Set water level switch to
enable
0-No alarm
1 - alarm
0
Sensor port 1 E_S1
Sensor fault alarm in
input port 1
0-No alarm
1 - alarm
1
Sensor port 2 E_S2
Sensor fault alarm in
input port 2
0-No alarm
1 - alarm
0
Sensor port 3 E_S3
Sensor fault alarm in
input port3
0-No alarm
1 - alarm
0