Fig. 4
* For example :
High limit value : 100
Low limit value : 20
Alarm Hysteresis value : 5
a. The alarm relay will On when measuring
value up to 100. The alarm relay will Off
again when measuring value down to 95.
b. The alarm relay will On when measuring
value down to 20. The alarm relay will
Off when measuring value up to 25.
13