507787-01C
mrcool.com
Page 13 of 22
•
voltage and line voltage. Refer to the dimension
•
provided caps to seal holes not used.
•
installed electric heat) is given in Figure 14. Refer to
for proper installation.
USE COPPER CONDUCTORS ONLY
1.
2. Remove the air handler access panel.
3.
connection box.
4.
5. Replace the air handler access panel.
SIDE
TOP
Figure 11. Electrical Connections
NOTE:
in Figure 12.
TOP
SIDE
Figure 12. Control Panel Relocated to End Panel
208 Volt Conversion
1.
2. Remove the air handler access panel.
3.
panel as a reference, move the 2 connected black
transformer leads from the 240 volt terminal on the
transformer to the 208 volt terminal on the transformer.
Electrically ground air handler. Connect
Failure to do so can result in death or electrical
shock.
208 / 240 VOLT TRANSFORMER
PRIMARY
SECONDARY
240 Volts
208 Volts
Figure 13. Converting Unit from 240VAC to 208VAC