1

Duct

System

Filter

Integrated Control

Electric Heat Amps

Duct Static

5

Line Voltage

3

RETURN

AIR

SUPPLY

AIR

Temperature

8

Blower Motor Amps

6
7

Thermostat

9

2

4

Drain Line

Disconnect

Switch

ELECTRIC HEAT AMPS____________

8

8

7

5

DUCT SYSTEM
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
VOLTAGE CHECK
Supply Voltage ___________

Electrial Connections Tight

1

2

3

DRAIN LINE
Leak Free

4

TOTAL EXTERNAL STATIC (dry coil)

Supply External Static ______      ______

TEMPERATURE DROP (Cooling Mode)
Return Duct Temperature   ___________

THERMOSTAT
Adjusted and Programmed

Return External Static ______      ______
Total External Static = ______      ______

6

Supply Duct Temperature

 −

 ___________

Temperature Drop = ___________

TEMPERATURE RISE (Heating Mode)
Return Duct Temperature   __________
Supply Duct Temperature

 −

 __________

Temperature Rise = __________

Operation Explained to Owner

9

Explained Operation of System to Homeowner

Technician’s Name:_______________________Date Start

Up & Performance Check Completed__________

Installing Contractor’s Name_______________________
Installing Contractor’s Phone_______________________
Job Address____________________________________

Installing Date_______________________________
Air Handler Model #___________________________

INDOOR BLOWER AMPS___________
INDOOR BLOWER CFM____________

Low Voltage _____________

dry coil    wet coil

Figure 20. 

Summary of Contents for Signature MAHM CTA Series

Page 1: ...nual carefully before installation and keep it for future reference The Signature Series is NOT designed for amateur installation Installation SHOULD be performed by an authorized technician Please re...

Page 2: ...General 3 Requirements 3 Installation Clearances 4 Installation 4 Condensate Drain 7 Duct System and Filters 8 Brazing Refrigerant Lines 9 Sealing the Unit 12 Electrical Connections 12 16 Check Out Pr...

Page 3: ...2 368 DETAIL OF PIPING PLATE LIQUID LINE CONDENSATE DRAINS 2 Horizontal 1 3 4 44 3 4 19 2 3 4 70 3 1 2 89 PIPING PLATE 4 3 4 121 4 3 8 111 2 3 8 60 CONDENSATE DRAINS 2 Upflow and Downflow SUCTION LIN...

Page 4: ...njury Take and protective clothing Requirements can result in back or other type of injury MAHM CTA units include a factory installed check capacities These units must be installed as a part of a matc...

Page 5: ...ld cabinet they exit the conduit opening Sealant is required to prevent air leakage into and condensate from forming inside of the air handler the control box and on the electrical controls This unit...

Page 6: ...air discharge horizontal applications Adequate support panels if installing in the horizontal position Right Hand Discharge 1 connections 2 With access door removed remove drain line plugs to install...

Page 7: ...op cap has a 45 bend on one side and a 90 bend on the other The 90 bend must be on the same side as the horizontal drain pan as illustrated in Figure 4 DOWN FLOW RAIL FRONT EDGE OF HORIZONTAL DRAIN PA...

Page 8: ...AIR HANDLER DRAIN PAN WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE A 3 4 19 1MM SECONDARY DRAIN LINE MUST BE CONNECTED TO SECONDARY DRAIN PAN OR CONNECTED TO THE OVERFLOW DRAIN OUTLET OF THE AIR HAN...

Page 9: ...ap in the main primary drain lines as close to the unit as practical see Figure 7 Make sure NOTE NOTE 7 Route the drain line to the outside or to an appropriate drain Drain lines must be installed so...

Page 10: ...e 018 024 030 036 042 048 060 18 3 8 21 1 2 Figure 9 Cabinet and Duct Flange Brazing Refrigerant Lines Refrigerant lines must be clean dry refrigerant grade copper lines Air handler coils should be in...

Page 11: ...th and that neither suction nor 3 To avoid damaging the rubber grommets in the cabinet source NOTE suction line connections 4 Connect the suction and liquid lines to the evaporator coil Take care to p...

Page 12: ...CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR UNIT FOR LEAK TESTING EVACUATING AND CHARGING PR...

Page 13: ...e foil faced insulation comes in provide a path for current to pass through to the outer metal cabinet While the current produced may not be enough to trip existing electrical safety devices e g fuses...

Page 14: ...Figure 11 Electrical Connections NOTE in Figure 12 TOP SIDE Figure 12 Control Panel Relocated to End Panel 208 Volt Conversion 1 2 Remove the air handler access panel 3 panel as a reference move the...

Page 15: ...507787 01C mrcool com Page 14 of 22 Figure 14 Typical Wiring Diagram MAHM CTA...

Page 16: ...507787 01C mrcool com Page 15 of 22 Figure 15 Typical Wiring Diagram MAHM CTA...

Page 17: ...EE NOTE SEE NOTE SEE NOTE Y Y AIR CONDITIONER UNIT R G BU W BK CONNECT COMMON WIRE ONLY IF REQUIRED REFER TO THE APPROPRIATE THERMOSTAT INSTALLATION INSTRUCTIONS AIR HANDLER THERMOSTAT HEAT PUMP UNIT...

Page 18: ...0 WC 018 LOW 538 525 503 471 418 MED 688 670 639 603 548 HIGH 919 881 855 788 710 024 LOW 677 673 657 629 592 MED 1011 979 942 803 742 HIGH 1106 1045 999 917 857 030 LOW 871 870 853 812 769 MED 1078 1...

Page 19: ...g cooled air 4 Set the thermostat 5 F higher than the indoor should cycle off 1 Set thermostat to call for auxiliary heat approximately minimum of 3 minutes for all sequencers to cycle on 2 Set the th...

Page 20: ...temperature and humidity and the varying conditions inside the unit If the insulation inside surface temperature of the cabinet and outside of the cabinet can cause condensation on the corrosion and s...

Page 21: ...Air Handler During Construction It is not recommended to use this air handler unit during any Air handler units may be used for heating heat pumps conditions are met A room thermostat must control the...

Page 22: ..._____ TEMPERATURE DROP Cooling Mode Return Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temper...

Page 23: ...eturn External Static ______ ______ Total External Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature _____...

Page 24: ...d or manual are subject to change without prior notice Consult with the sales agency or manufacturer for details Signature Series MAHM CTA Air Handler ELECTRICIAN and or HVAC TECHNICIAN LICENSE INSTAL...

Reviews: