Safety Requirements
Caution!
To reduce risk of electrical shock, equipment damage, and fire and to
maintain proper operation, ensure that the safety requirements stated
hereunder are met!
Before Installing
Power
Ensure that
all
power to the LDx00 is cut off. Specifically, disconnect all LDx00
power cords from the power source/s (line/mains).
Inspection
Ensure by inspection that no part is damaged.
Covers
Leave the protective covers (e.g., dust caps on optical connectors, etc.) on the
LDx00 at all times until it is about to be installed.
Site
Reserve one of the following sites for the LDx00:
LD400
−
482 x 89 or 2U
x 324 mm
3
(19 x 3.5 or 2U x 12.8 in
3
) space in a 19-
inch rack,
or
−
Flat, stable, non-conductive static-free surface.
LD800
−
482 x 200 or 4.5U x 267 mm
3
(19 x 7.8 or 4.5U x 10.5 in
3
) space in a
19-inch rack,
or
−
Flat, stable, non-conductive static-free surface.
Before Powering On
Blank Panels
Ensure that vacant slots of the LDx00 are covered with Blank Panels. (This
protects the user against electrical shock and the LDx00 against harmful physical
intrusion, and increases operation reliability by assuring circulation of sufficient
cooling air throughout the LDx00.)
Temperature
Operate the LDx00 only at a location where the ambient temperature is in the
range 0 to 45
o
C (32 to 113
o
F).
Humidity
Operate the LDx00 only at a location where the ambient humidity is non-
condensing and less than 85%.
Dust
Ensure that the site for the LDx00 is dust-free. (Less than 1,000,000 particles per
cubic meter or 30,000 particles per cubic foot is OK.)
Cooling Air
Ensure that the air-flow around the LDx00 and through the air vents is not
obstructed. In addition, ensure that there is a clearance of at least 25 mm (1 inch)
between the air vents and nearby objects.
Power
Ensure that the power to the LDx00 is:
2
1U = 1¾ inch or 44.45 mm
18