Command 133: Set Alarm Relay Action
Set the action/mode of the Alarm Relay.
Request Data Bytes:
Byte
Format
Description
0
Unsigned-8
0=Latching (default)
1=Sentry
2=Non-Latching
Command Specific Response Data Bytes:
Byte
Format
Description
0
Unsigned-8 Response Code
1
Unsigned-8 Device Status
2
Unsigned-8 Returns new value of Alarm Relay Action Variable
Command 134: Set Warning Relay Action
Set the action/mode of the Warning Relay.
Request Data Bytes:
Byte
Format
Description
0
Unsigned-8
0=Latching
1=Sentry
2=Non-Latching (default)
Response Data Bytes:
Byte
Format
Description
0
Unsigned-8 Response Code
1
Unsigned-8 Device Status
2
Unsigned-8 Returns new value of Warning Relay Action Variable
56
SMC 5100-XX-IT Toxic Gas Detector Module
13 HART
US