Command 150: Write MODBUS RTU 16-bit Register (using index)
This command allows the writing to the sensor module 16-bit MODBUS registers as defined in the MODBUS RTU register
map. The index provided is 1 byte and is referenced from address 40000.
The unsigned 16-bit data that is written is provided in floating point format.
Request Data Bytes:
Byte
Format
Description
0
Unsigned-8 Index to select register, with 40000 offset removed
1-4
Float
Float Value to be written to Modbus register
Response Data Bytes:
Byte
Format
Description
0
Unsigned-8 Response Code
1
Unsigned-8 Device Status
2
Unsigned-8 Index of select register with 40000 offset removed
3-6
Float
New value of register
SMC 5100-XX-IT Toxic Gas Detector Module
61
US
13 HART