MSA AUER
MSA
Operation of the System
SUPREMATouch
37
US
Normal [energised]
Field type: Selection
Set the operating mode for the selected relay output:
-
Normally energised [“closed circuit”]:
The relay coil is energised in the no alarm status and is de-energised in the alarm status.
-
Normally de-energised [“open circuit”]:
The relay coil is de-energised in the no alarm status and is energised in the alarm status.
Tag
Field type: Text
Enter a customer-specific designation for the selected relay output.
blk. [flashing]
Field type: Checkbox
If this field is set, the relay flashes at a frequency of approx. 1 Hz when activated. This function
doesn't work together with the inhibit condition.
New Alarm [i. e. actual alarm]
Field type: Check box
If this field is set, the relay output selected can be set to “normal” status by pressing the <ACKNL>
key even if the signal value has been outside the alarm threshold limits.
OK
Field type: Button
Tapping this button validates the settings entered for the selected relay output. When the button
is tapped, the voting settings must not be higher than the number of conditions set in the check
boxes. If this is the case, they become part of the system’s parameter set. If not, a warning ap-
pears.
Cancel
Field type: Button
Pressing this button discards the settings entered for the selected relay output.
Clear
Field type: Button
Pressing this button deletes all of the parameters for the selected relay output. The output then
returns to the status it was before it was set up the first time.
Summary of Contents for SUPREMA Touch
Page 2: ...Manual SUPREMATouch Fire and Gas Warning Unit Order No 10126972 00...
Page 7: ...SUPREMATouch 6 Contents MSA US...
Page 8: ...User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Page 104: ...Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Page 112: ...Installation and Start Up Manual SUPREMATouch Fire and Gas Warning Unit...
Page 151: ...SUPREMATouch 150 Installation MSA US Fig 79 MCP Module standard configuration...
Page 303: ...SUPREMA 302 Dimensions MSA GB 16 Dimensions 16 1 Rack...
Page 306: ...MSA AUER MSA Dimensions SUPREMA 305 GB MRO20 8 TS Module 1 3 2 69 90...
Page 307: ...SUPREMA 306 Dimensions MSA GB MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Page 308: ...MSA AUER MSA Dimensions SUPREMA 307 GB MRC TS Module MGT 40 TS Module...
Page 309: ...SUPREMA 308 Dimensions MSA GB MHD TS Module MAT TS Module...