2 Installation
Electronics can be destroyed by electrostatic discharge (ESD). Therefore the installation work
should be done only by persons connected to ground, e. g. by standing on a conductive floor or
by taking appropriate grounding measures (acc. to DIN EN 100015).
2.1 Mounting Instructions
See description of the SB2, MSC2 and MSB2 devices.
When choosing the mounting site please pay attention to the following:
The mounting height depends on the relative density of the gas type to be monitored.
Gas type
MSR-Code
Relativ density
(air = 1)
Recommended mounting height
(distance to floor / ceiling)
Ammoniak
E1125
0.59
Ceiling (0.3 m)
Chlor
E1193
2.40
Floor (0.2 - 0.3 m)
Fluorwasserstoff
E1182
0.71
Ceiling
Cyanwasserstoff
E1183
0.93
Ceiling (0.3 m)
Chlorwasserstoff
E1186
1.25
Floor (0.3 - 0.8 m)
Ethylen
E1189
0.97
1.5
– 1.8 m
Fluor
E1198
1.31
Floor (0.2 - 0.3 m)
Formaldehyd
E1185
1.09
Floor (0.3 - 0.8 m)
Kohlenmonoxid
E1110
0.97
1.5
– 1.8 m
Ozon
E1190
1.66
Floor (0.3 m)
Phosphin
E1187
1.18
Floor (0.8 m)
Schwefeldioxid
E1196
2.26
Floor (0.2 - 0.3 m)
Schwefelwasserstoff
E1197
1.19
Floor (0.2 - 0.3 m)
Silan
E1188
1.16
Floor (0.8 m)
Stickstoffdioxid
E1130
1.59
1.5
– 1.8 m
Stickstoffmonoxid
E1129
1.04
1.5
– 1.8 m
Sauerstoff
E1195
1.10
1.5
– 1.8 m
Table Mounting Heights
Choose mounting location of the sensor according to the local regulations.
Consider ventilation conditions! Do not mount the sensor near the airflow (air passages, suction holes
etc.).
Mount the sensor at a location with minimum vibration and minimum variation in temperature (avoid
direct sunlight).
Avoid locations where water, oil etc. may influence proper operation and where mechanical damage
might be possible.
Provide adequate space around the sensor for maintenance and calibration work.