dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 001 24
Torque Ratings
Table 5-1: Torque Ratings
Filter
Rating
(Amps)
dV E-Series Terminals
Input /Output Power
U1-V1-W1 / U2-V2-W2
Resistor Terminals (Kits ONLY)*
Recommended
Minimum
Wire Size
(AWG)
Terminal Torque
(in-lbs.)
Recommended Wire Size
(AWG)
Terminal
Torque
(in-lbs.)
3 - 12
14
16
16
N/A
17
12
16
14
N/A
22
10
16
14
N/A
27
10
16
14
N/A
35
8
16
14
N/A
45
8
16
14
N/A
55
6
16
14
N/A
65
6
N/A
14
N/A
80
4
N/A
14
N/A
110
2
N/A
14
N/A
130
1
N/A
14
16
160
4(2x) or 2/0
N/A
14
16
200
3(2x) or 3/0
N/A
14
16
250
1 (2x) or 250kcmil
N/A
14
16
305
2/0 (2x)
N/A
14
16
365
3/0 (2x)
N/A
14
16
415
4/0 (2x)
N/A
14
16
515
300kcmil (2x)
N/A
14
16
600
350kcmil(2x)
N/A
14
16
750
N/A
14
16
NOTE: Kit versions of the dV E-Series ship with a reactor and resistor only. Wiring between these
components is the responsibility of the customer and should follow the recommended wire size
listed above under “Resistor Terminals.” All other versions of the dV E-Series are pre-wired.
NOTE: To prevent flexing or bending of the coil windings attached to dV E-Series filter, use
appropriate strain relief to prevent stress on terminals. For flat copper terminal tabs, use two
wrenches to tighten customer provided cable mounting hardware.
NOTE: Wiring should be UL 1199, Class N (200° C)