HYDROCAL 1005 Manual for Installation and Operation
Page 88/111
A message in the field "Message" can be pre-write in order to be sent to the recipient in the event of
alarms while using pre-
send message. For this, In the field “message” click on right mouse button
and click on Insert to visualize followings pre-send messages:
To add pre-send message, you have to click on them. The following possibilities are available:
{#}- Serial Number: means that in the event of alarms, you will receive a SMS with serial number
of the unit
{1}- Custom Line 1: means that in the event of alarms, you will receive a SMS with customer 1
st
line displayed on the main HYDROCAL1005 Menu
{2}- Custom Line 2: means that in the event of alarms, you will receive a SMS with customer 2
nd
line displayed on the main HYDROCAL1005 Menu
{3}- Custom Line 3: means that in the event of alarms, you will receive a SMS with customer 3
rd
line displayed on the main HYDROCAL1005 Menu
{4}- Custom Line 4: means that in the event of alarms, you will receive a SMS with customer 4
th
line displayed on the main HYDROCAL1005 Menu
{T}- Long Time: Means that in the event of alarms, you will receive a SMS with Time of alarm
which has been exceeded with following format: “hh:mm:ss”
{t}- Short Time: Means that in the event of alarms, you will receive a SMS with Time of alarm
which has been exceeded with following format: “hh:mm”
{D}- Long Date: Means that in the event of alarms, you will receive a SMS with Date of alarm
which has been exceeded with following format: “YYYY:MM:DD”
{d}- Short Date: Means that in the event of alarms, you will receive a SMS with Date of alarm
which has been exceeded wit
h following format: “YY:MM:DD”
{A}- Alert Name: means that in the event of alarms, you will receive a SMS with the alarm Name
{a}- Alert Number: means that in the event of alarms, you will receive a SMS with Alert Number
{l}- Alert Level: means that in the
event of alarms, you will receive a SMS with Alert Level (“1” for a
High alarm or Level 1 and “2” for a High-High alarm or Level 2)
Note: You can combine the variable between them in order to have requested Alarm SMS informa-
tion (e.g. {#}{1}{T}{D}{A}{l})
A message in the field "Message" can also be free pre-write in order to be sent to the recipient in the
event of alarms.
Note: The SMS mode (in Alarm setup) must be selected to use this function. A GSM / Analogue mo-
dem must be also installed in HYDROCAL1005.
Data in the tree
are changed after modification of sensor settings and validation
with
. The star indicates that modifications have been made; these must be transferred to
the HYDROCAL1005 unit for activation. This means, the settings indicated are not identical to those
of HYDROCAL1005. With next connection, it is requested whether the settings on HYDROCAL1005
unit shall be updated (see chapter 5.11).