background image

Matrix

®

 E-Series Technical Reference Manual 380V – 480V

 

17  

       Form: MAE-TRM-E September 2020 REV. 001 

Power Wiring Connection 

 

Verify that the power source to which the filter is to be connected is in agreement with the nameplate 

data on the filter. A fused disconnect switch or circuit breaker should be installed between the drive and 

its source of power in accordance with the requirements of the NEC and all local electrical codes and 

regulations. Refer to the drive user manual for selection of the correct fuse rating and class.  

 

Refer to the drive user manual for instructions on interconnecting the drive and motor and the correct 

start-up procedures for the drive.   

 

The filter is designed for use with copper conductors with a minimum temperature rating of 75 degrees 

C.  

 

Wiring Checks 

 

Using Figure 5-1: Basic Schematic Diagram

 (p18) 

visually check the wired components to confirm, 

verify, and correct wiring. Then, with a multi meter, check phase to phase isolation using the 100 K ohm 

range. The multi meter will read the parallel equivalent of the bleeder resistors after the capacitors 

initially charge. All phase to phase resistance values should be the same. 

 

Check for the Following Faults:

  

 

  Capacitor shorted 

  Capacitor bus not connected 

  Capacitor bus to chassis short 

  Paralleling wiring errors 

 

 

 

WARNING

 

Input and output power wiring to the filter should be performed by authorized 

personnel in accordance with the NEC and all local electrical codes and 

regulations. 

Cable lugs and mounting hardware are provided by the customer. 

Any extremely low or high resistance readings indicate miswiring and may 

result in damage to filter components if not corrected. 

Summary of Contents for MAEP0006C

Page 1: ...AL WARNING High Voltage Only a qualified electrician can carry out the electrical installation of this filter Quick Reference Performance Data Pages 5 10 Selection Guide Pages 11 14 Installation Guide...

Page 2: ...This page intentionally left blank...

Page 3: ...OR CURRENT 7 TYPICAL HARMONIC SPECTRUM 8 MATRIX E SERIES LOAD VS POWER FACTOR 8 TYPICAL PERFORMANCE WITH UNBALANCED LINE VOLTAGE 9 ALTITUDE DERATING 9 VOLTAGE DISTORTION DERATING 10 4 HOW TO SELECT 11...

Page 4: ...Diagram 18 Figure 5 2 Open Panel Interconnection 19 List of Tables Table 3 1 Performance Specifications 5 Table 3 2 Filter Efficiency Watt Loss Capacitor Current 6 Table 3 3 Filter Efficiency Watt Los...

Page 5: ...lead to serious injury or death WARNING General Warning warns of situations that can result in serious injury or death if proper precautions are not used Caution General Caution identifies situations...

Page 6: ...erminals Only spare parts obtained from MTE Corporation or an authorized MTE distributor can be used After removing power allow at least five minutes to elapse and verify that the capacitors have disc...

Page 7: ...tatement Upon Receipt of this Filter The Matrix E Series Harmonic Filter has been subjected to demanding factory tests before shipment Carefully inspect the shipping container for damage that may have...

Page 8: ...nd Agency Approvals Standards CSA C22 2 No 14 95 CE EN50178 1997 Support in the compliance of IEEE 519 Agency Approvals UL and cUL listed to UL508 Type MAE CE Marked RoHS Compliant REACH Compliant War...

Page 9: ...ad 17 40 load System Power Conditions at Rated Current THVD 2 Line Voltage Unbalance 1 Source Impedance Maximum 6 Minimum 1 5 Maximum output voltage at no load RMS Peak 5 Minimum output voltage at ful...

Page 10: ...ncy Typical Power Dissipation Watts Typical Capacitor Current Amps RMS 6 98 5 65 2 4 8 98 7 74 3 2 11 98 8 94 4 4 14 98 9 106 5 6 21 98 7 192 8 4 27 98 9 212 10 8 34 99 1 205 13 6 44 99 1 270 17 6 52...

Page 11: ...y Typical Power Dissipation Watts Typical Capacitor Current Amps RMS 6 98 3 70 2 2 8 98 4 79 2 9 11 98 3 101 4 0 14 98 5 113 5 0 21 98 6 205 7 6 27 98 5 227 9 7 34 98 7 219 12 2 44 98 8 289 15 8 52 99...

Page 12: ...Reference Manual 380V 480V Form MAE TRM E September 2020 REV 001 8 Typical Harmonic Spectrum Figure 3 1 Typical Harmonic Spectrum with and without Matrix E SERIES Matrix E Series Load vs Power Factor...

Page 13: ...Table 3 4 Typical Performance with Unbalanced Line Voltage All Components at Nominal Values and Worse Case Service Conditions 100 Load Nominal THID 11 39 1 Unbalance 11 45 2 Unbalance 11 50 3 Unbalanc...

Page 14: ...a Matrix E Series harmonic filter in environments with a preexisting voltage distortion Example In a system with 10 voltage distortion a Matrix filter will need to be oversized by 5 5 to obtain the sa...

Page 15: ...e use of information circuits or equipment described in this instruction manual Matrix E Series harmonic filters are available in Open Panel configurations For inverters feeding isolation transformers...

Page 16: ...AE TRM E September 2020 REV 001 12 Model Number Code System MAE P _ _ _ _ x Matrix E Series Enclosure Type P Panel Mount No Enclosure Current Rating 0006 is 6 Amps 0083 is 83 Amps 0320 is 320 Amps Vol...

Page 17: ...44 MAEP0044C 43 20 12 0 x 7 1 x 6 1 305 x 180 x 155 10 6 x 4 6 269 x 117 52 MAEP0052C 55 25 14 5 x 9 6 x 6 9 368 x 244 x 175 9 1 x 4 6 7 5 x 3 9 231 x 117 191 x 99 66 MAEP0066C 60 27 14 6 x 9 6 x 6 7...

Page 18: ...305 x 180 x 155 7 5 x 3 0 9 1 x 4 6 191 x 76 231 x 117 52 MAEP0052D 53 24 14 5 x 9 6 x 6 9 368 x 244 x 175 9 1 x 4 6 231 x 117 66 MAEP0066D 56 25 14 6 x 9 6 x 6 7 371 x 244 x 170 7 5 x 3 0 10 6 x 4 6...

Page 19: ...etween the reactor and capacitor is required by the customer Open panel Matrix E Series filters are designed for mounting within the customer s enclosure When determining the internal temperature rise...

Page 20: ...he drive to prevent filter damage due to abnormal operating conditions The temperature switch is normally closed and will open when an internal reactor temperature of 180 C is reached See Table 5 1 Ov...

Page 21: ...minimum temperature rating of 75 degrees C Wiring Checks Using Figure 5 1 Basic Schematic Diagram p18 visually check the wired components to confirm verify and correct wiring Then with a multi meter...

Page 22: ...Matrix E Series Technical Reference Manual 380V 480V Form MAE TRM E September 2020 REV 001 18 Matrix E Series Schematic Diagram Figure 5 1 Basic Schematic Diagram...

Page 23: ...ries Technical Reference Manual 380V 480V 19 Form MAE TRM E September 2020 REV 001 Matrix E Series Interconnection Diagram Figure 5 2 Open Panel Interconnection MATRIX E Series OPEN PANEL INTERCONNECT...

Page 24: ...14 23 21 14 6 16 16 CAP 344TP 14 23 27 14 6 16 16 CAP 345TP 14 23 34 14 6 16 16 CAP 346TP 12 23 44 14 6 16 16 CAP 347TP 12 23 52 Flat copper tab N A 16 CAP 346TP CAP 342TP 10 23 66 Flat copper tab N...

Page 25: ...TP 14 23 27 14 6 16 16 CAP 343TP 14 23 34 14 6 16 16 CAP 349TP CAP 343TP 12 23 44 14 6 16 16 CAP 339TP CAP345TP 12 23 52 Flat copper tab N A 16 CAP 346TP 10 23 66 Flat copper tab N A 16 CAP 347TP CAP...

Page 26: ...ng to the utility drive and motor is in accordance with the power wiring connection diagrams shown in installation instructions section 3 Check that moisture has not condensed on the filter components...

Page 27: ...alified personnel only and in accordance with OSHA Regulations High voltage is used in the operation of this filter Use Extreme caution to avoid contact with high voltage when operating installing or...

Page 28: ...00K ohms check a Phase to phase U1 V1 W1 U1 mechanically activate contactor if present after reactor and caps charge reading should be about 40K total equivalent breeder resistance value Open circuit...

Page 29: ...EM Filter output voltage is not within specification Possible cause Filter input voltage is not within specification Solution Check the AC input line voltage and verify that it is within tolerance Ref...