Matrix
®
E-Series Technical Reference Manual 380V – 480V
21
Form: MAE-TRM-E September 2020 REV. 001
Matrix E-Series 480V Torque Ratings
Table 5-3: Torque Ratings 480V
Filter
Rating
(Amps)
Reactor Terminals
Capacitor Terminals
U4-V4-W4
Input /Output Power
U1-V1-W1 / U2-V2-W2
Interconnect
Reactor
U4-V4-W4
Capacitor
Part Number
Minimum
Interconnect
Wire Gauge
(AWG)
Terminal
Torque
(in-lbs.)
Recommended
Minimum Wire
Gauge
(AWG)
Terminal
Torque
(in-lbs.)
Terminal
Torque
(in-lbs.)
6
14-6
16
16
CAP-339TP
14
23
8
14-6
16
16
CAP-349TP
14
23
11
14-6
16
16
CAP-365TP
14
23
14
14-6
16
16
CAP-341TP
14
23
21
14-6
16
16
CAP-342TP
14
23
27
14-6
16
16
CAP-343TP
14
23
34
14-6
16
16
CAP-349TP /
CAP-343TP
12
23
44
14-6
16
16
CAP-339TP /
CAP345TP
12
23
52
Flat copper tab
N/A
16
CAP-346TP
10
23
66
Flat copper tab
N/A
16
CAP-347TP/
CAP-339TP
10
23
83
Flat copper tab
N/A
16
CAP-345TP /
CAP-346TP
10
23
103
Flat copper tab
N/A
16
CAP-348TP /
CAP-343TP
10
23
128
Flat copper tab
N/A
N/A
CAP-347TP (2)
10
23
165
Flat copper tab
N/A
N/A
CAP-348TP (2) /
CAP-340TP
10
23
208
Flat copper tab
N/A
N/A
CAP-348TP (2) /
CAP-343TP (2)
8
23
240
Flat copper tab
N/A
N/A
CAP-338TP (2) /
CAP-345TP /
CAP-346TP
4
23
320
Flat copper tab
N/A
N/A
CAP-348TP (4) /
CAP-340TP
2
23
Note: To prevent flexing or bending of the coil windings attached to the flat copper terminal tabs
on the Matrix E-Series reactor, use two wrenches to tighten customer provided cable mounting
hardware.