Matrix Series D Users Manual
Filter Description -continued
42
Part No.
INSTR-025 REL. 071207
Contactor coil switching currents
Table 11
Options 002, 010 &011
The following table indicates the 120 VAC 50 Hz current required to switch and hold the various size
contactors used in Matrix Filter® capacitor switching and bypass options. This data is provided to select
the proper switch rating to remotely control the contactor.
Contactor Currents for 120 VAC 50 Hz coils.
Capacitor Contactor Option 002
AMPS (Maximum)
Filter Bypass Options 010 & 011
AMPS (Maximum)
Matrix Filter®
current Rating
AMPS
INRUSH SEALED INRUSH SEALED
6 0.54 0.10 0.54 0.10
8 0.54 0.10 0.54 0.10
11 0.54 0.10 0.54 0.10
14 0.54 0.10 0.54 0.10
21 0.54 0.10 0.54 0.10
27 0.54 0.10 0.54 0.10
34 0.54 0.10 0.54 0.10
44 0.54 0.10 1.7 0.30
52 0.54 0.10 1.7 0.30
66 0.54 0.10 2.44 0.60
83 0.54 0.10 3.79 0.40
103 0.54 0.10 3.79 0.40
128 0.54 0.10 4.95 1.00
165 1.70 0.30 10.6 1.3
208 1.80 0.30 11.95 1.4
240 3.25 0.40 11.95 1.4
320 8.70 1.00 11.95 1.4
403 8.70 1.00 -
-
482 8.70 1.00 -
-
636 8.70 1.00 -
-
786 8.70 1.00 -
-