8.6 Fieldbus
Terminating
A fieldbus terminator is required at both ends of the trunk.
Spurs are operated without terminating resistors.
Fieldbus Barrier is located at the end of the trunk
In this case, the terminals on the "TRUNK OUT" terminal block are not to be used.
Remove the factory-provided jumper from its storage position (1).
Insert the jumper in terminals "1" and "2" on the terminal block (2).
Close/screw tight the terminals.
The built-in terminator is activated.
Fieldbus Barrier is not located at the end of the trunk
The terminals on the terminal block are not to be used.
Ensure the factory-provided jumper is in its storage position (1).
The built-in terminator is not activated.
Figure 13: - Terminator jumper fitted
Figure 14: - Terminator jumper not required