Fault
code no.
Full designation
Meaning
Action
Setting parame-
ter no.
413
HIHI U-PDU
Injector voltage too high (lim-
it value 2, alarm configura-
tion parameter, see PR
2.8008.100 for explanation).
Execute engine gov-
ernor self-test, re-
place engine gover-
nor in case of fault.
2.0141.932
444
SD U-PDU
SD alarm configuration, sen-
sor fault at injector output
stage. Engine governor inter-
nal fault. Engine governor re-
placement.
Replace engine gov-
ernor.
1.8004.578
450
SD Idle/End-Torque In-
put [%]
SD alarm configuration, input
signal for initial/final torque
faulty, short circuit or wiring
damage
Check signal trans-
mitter and wiring,
replace as necessa-
ry. Fault is rectified
when engine is re-
started.
2.8006.592
454
SS Power Reduction
Active
Power reduction activated,
engine operating outside
standard limits. The following
variables may also combine
to lead to this message: In-
take depression, exhaust
back pressure, charge-air
coolant temperature, intake
air temperature. Alarm con-
figuration parameter, see PR
2.8008.100 for explanation.
None.
2.7000.011
463
SD AUX 2
SD alarm configuration, ana-
log input signal for Aux 2
faulty, short circuit or wiring
damage.
Check signal trans-
mitter and wiring,
replace as necessa-
ry.
1.8004.591
464
SD P-AUX 1
SD alarm configuration, ana-
log input signal for pressure
Aux 1 faulty, short circuit or
wiring damage.
Check pressure
transmitter and wir-
ing, replace as nec-
essary.
1.8004.589
468
SD T-AUX 1
Analog input for temperature
Aux 1 faulty, short circuit or
wiring damage
Check signal trans-
mitter and wiring,
replace as necessa-
ry.
1.8004.579
469
SD AUX 1
SD alarm configuration, ana-
log input signal for Aux 1
faulty, short circuit or wiring
damage.
Check signal trans-
mitter and wiring,
replace as necessa-
ry.
1.8004.590
470
SD T-ECU
Engine governor defective.
Replace engine gov-
ernor at next oppor-
tunity.
1.8004.587
471
SD Coil Current
SD alarm configuration, HP
fuel control block activation,
short circuit or wiring dam-
age.
Check sensor and
wiring, replace as
necessary. Fault is
rectified when en-
gine is restarted.
1.8004.592
62 | Troubleshooting | MS15018/02E 2013-09
TIM-ID: 0000008508 - 003