94 – LO T-Preheat
Yellow alarm; warning
Cause
Corrective action
Preheating temperature too low
(Level 1); coolant temperature
too low for engine start.
1. Extend preheating period.
2. Check preheater.
95 – AL Prelubrication Fault
Yellow alarm; warning
Cause
Corrective action
Oil priming fault
u
Contact Service.
102 – AL Fuel Cons. Meter Defect
Yellow alarm; warning
Cause
Corrective action
Consumption meter faulty.
u
Replace Engine Control Unit at next opportunity.
104 – AL Eng Hours Counter Defect
Yellow alarm; warning
Cause
Corrective action
Hour meter faulty.
u
Replace Engine Control Unit at next opportunity.
118 – LO ECU Supply Voltage
Yellow alarm; warning
Cause
Corrective action
Supply voltage too low (Level 1).
u
Check batteries, charge as necessary; check alternator.
119 – LOLO ECU Power Supply Voltage
Yellow alarm; warning
Cause
Corrective action
Supply voltage too low (Level 2).
u
Check batteries, charge as necessary; check alternator.
120 – HI ECU Supply Voltage
Yellow alarm; warning
Cause
Corrective action
Supply voltage too high (Level
1).
u
Check batteries, charge as necessary; check alternator.
MS150118/01E 2015-05
| Troubleshooting | 69
TIM-ID: 0000060724 - 001