5.4 Starting the engine in emergency situations (override mode)
NOTICE
Safety functions and engine shutdown alarms will be disregarded.
Severe material damage!
• Initiate emergency start only in emergency situations.
Preparation
Item
Measure
Operating mode switch
Change to override mode (manual mode, if applicable).
Starting the engine in emergency situations
Item
Measure
Control cabinet
Actuate switch/button for ECU override input.
Control cabinet
• Automatic starting procedure is performed; any safety functions and
alarms leading to engine shutdown are disregarded;
• Engine speed display instrument indicates increasing speed;
• After the starting sequence is completed, engine is running at rated
speed.
Connecting the generator (if fitted) to mains
Item
Measure
Control cabinet
If generator is not connected to mains: Close the generator circuit breaker.
Engine
Operate engine at rated power.
46 | Operation | M015565/03E 2016-02