HG-2 LOW-PROFILE DIRECT DISCHARGE UNIT
TROUBLESHOOTING THE PROGRAMMER
Troubleshooting
TROUBLESHOOTING THE UNIT
control knob Is open on the
valve OR Check the pipes for
obstructions OR Check the
valve.
• Check the water pressure at
the unit. The pressure must be
in the operating range of the
solenoid and programmer (150
psi maximum). If too high a
PRV might need to be installed.
The Hydro-Guard Unit will not shut
off:
Possible Causes
• The solenoid is stuck In the
open position.
• Batteries weak or dead.
• Connection loss from controller
to solenoid.
• The solenoid is loose or there
is debris in the adapter.
• There is a hole in or debris
around the diaphragm.
If your Hydro-Guard Unit does not
activate:
Possible Causes
• Water pressure off or low.
• Batteries weak or dead.
• Connection loss from controller
to solenoid.
• Solenoid not working properly.
• Obstruction In flow of water.
• The water pressure is too high
and the solenoid will not open.
Try this Correction
• Check if curb stop is open.
• Change batteries.
• Check connections for
corrosion, breaks, or lack
of connection.
• Run an electrical systems
check.
• Check to make sure the flow
• The water pressure Is too high
and the solenoid will not close.
Try this Correction
• Run a manual flush for 1
minute.
• Change batteries.
• Check connections for
corrosion, breaks, or lack of
connection.
• Check the adapters and
solenoid for debris. Run the
electrical systems check.
• Refer to valve troubleshooting
for possible corrective
measures.
• Check the water pressure at
the unit. The pressure must be
in the operating range of the
solenoid and programmer (150
psi maximum). If too high a PRV
might need to be installed.
PROBLEM CAUSE
SOLUTION
Controller does not flush
as desired
Water at main water supply is
shut off
Battery dead
Replace battery
Battery dead
Replace battery
Controller improperly programmed
Check program and clock settings
Controller set to OFF
Set controller to desired program
Blank display
Water does not turn off
Overlapping programming
Review all programming and edit
any program that is in conflict with
desired off schedule
Clear all programming in memory
and reset
Programmer not communicating
Check Programming
Run Manual On / Off with solenoid
removed from valve (hold finger
or object over solenoid plunger to
prevent plunger from dislodging
from solenoid body)
Check wiring for damage and
connectors to ensure proper
connection (red to red & black
to black)
Check main supply valve