Bakery Chiller Models PMC 40/50 and PMC 70/120
Effective February 23, 1999
Installation and Operation Instructions, Part No. 9842311
Revised May 7, 2009
SECTION 2.0 - INSTALLATION
2.1 Inspection
Because it is possible for equipment to be damaged during shipment, we recommend that you make a
thorough inspection of all equipment before it is unloaded from the freight truck. Carefully inspect
equipment for hidden damage. It may be difficult to collect for damage if it is not found prior to
unloading. It is very important to note any damage on the bill of lading and have the driver sign it.
2.2 Safety
Installation and service should be performed by an authorized service technician who has the proper
training to install and service refrigeration equipment. Effective November 1994, the service technician
must be certified in refrigerant usage by an EPA-approved testing organization prior to installing or
servicing any refrigeration equipment.
All electrical connections must be performed by a qualified electrician in accordance with local and
NEC regulations.
2.3
Location
When choosing a location for the Mueller bakery chiller, consider these items:
•
Environment:
An indoor location will be necessary where the chiller section is protected from
freezing temperature.
•
Serviceability:
The chiller should be located with the circulating pump and the control panel
accessible for service. Keep in mind the chiller will require field connections to the main electrical
supply and water supply line. The chiller should be located close to a drain for service and
cleaning.
•
Refrigeration Unit:
The refrigeration unit (for PC and RC models) must be located where they are
protected from the environment and have adequate air-flow for the condenser. Be especially
cautious of conditions that would allow dust or oil to enter the condenser.
•
Efficiency:
Locate the chiller as close as possible to point of use for chilled water.
2.4 Chilled Water Piping
The bakery chiller supply water should be connected to the
3
/
4
" inlet water solenoid valve located at
the top of the water tank (refer to Figure 3, “Flow Diagram”). The supply water line should be taken
from a source that provides adequate water flow and a minimum of
3
/
4
" in size. It is recommended that
a full flow shut-off valve and union be installed just prior to the solenoid valve for service.
The chilled water supply should be connected to the
3
/
4
" chilled water outlet located near the
circulation pump. Keep this line as short as possible to allow for chilled water of desired temperature
to be provided to point(s) of use. This line should be insulated to reduce external heat gain to the
chilled water.
Check all piping for leaks and repair if required. Clean and rinse lines and water storage tank prior to
usage.
3