Basket Fan

INS00131-A

Original instructions

ENGLISH (US) | 5

≤ 1.6 A

Cos φ ≥ 0.6

DC

≤ 12 V

≤ 40 A

Table 1: 

Maximum thermostat (TB) load

4.2.2

Speed control

Verify that this fan is suitable for speed control. On the datasheet and rating
plate the following (combination of) codes can be found:

F

 = suitable for frequency control / VFD (Variable Frequency Drive)

E

 = suitable for electronic voltage control (TRIAC / phase cutting)

T

 = suitable for transformer voltage control

WARNING

If none of these codes is listed, this fan cannot be speed con-
trolled!

Variable Frequency Drive (FC / frequency control)

• Do not reduce the frequency to less than 20% of the nominal frequency

as listed on the rating plate.

• When using a variable frequency drive, the wiring instructions of the vari-

able frequency drive manufacturer must be followed.

WARNING

Do  not  increase  the  frequency  beyond  the  nominal  value  as
listed on the rating plate

Electronic Voltage Control (TRIAC / SOLID-STATE / phase
cutting)

• Do  not  reduce  the  voltage  to  less  than  40%  of  the  nominal  voltage  as

listed on the rating plate.

• Motor noise (humming) can occur due to this type of control

Transformer voltage control

• Do  not  reduce  the  voltage  to  less  than  40%  of  the  nominal  voltage  as

listed on the rating plate.

For US only:

For 3~ fans only:

WARNING

To Reduce The Risk of Fire or Electric Shock, Do Not Use This
Fan With Any Solid-State Speed Control Device

For Canada only:

For 3~ fans only:

WARNING

NOT  SUITABLE  FOR  USE  WITH  SOLID-STATE  SPEED  CON-
TROLS

4.3

UL Installation instructions

WARNING

To reduce the risk of fire, electric shock, or injury to persons,
observe the following:

• Installation  work  and  electrical  wiring  must  be  done  by  qualified  per-

son(s) in accordance with all applicable codes and Standards, including
fire-rated construction.

• Sufficient air is needed for proper combustion and exhausting of gases

through  the  flue  (chimney)  of  fuel  burning  equipment  to  prevent  back
drafting.  Follow  the  heating  equipment  manufacturer's  guideline  and
safety Standards such as those published by the National Fire Protection
Association (NFPA), and the American Society for Heating, Refrigeration
and  Air  Conditioning  Engineers  (ASHRAE),  and  the  local  code  authori-
ties.

• When  cutting  or  drilling  into  wall  or  ceiling,  do  not  damage  electrical

wiring and other hidden utilities.

• Ducted fans must always be vented to the outdoors.

Hose down

This  fan  is  IP55  and  can  be  hosed  down  with  water.  The  installer  is  to  use
rigid  conduit  or  electrical  metallic  tubing  with  rain-tight  fittings,  or  liquid-tight
flexible metal or non-metallic conduit with acceptable fitting.

5

Commissioning

1 Impeller rotation direction

2 Airflow direction

Before initial start-up verify that:

1.

Installation and electrical connection have been properly completed.

2.

No foreign material is present within the fan and fan housing.

3.

All necessary safety devices such as guards are in place.

Initial start-up

1.

Briefly switch on the power supply and check if the impeller rotates in the
correct direction. Correct if necessary:

– For 3~ fans interchange any 2 of the 3 phases of the supply.

– For 1~ fans contact your supplier.

2.

Run the fan and check for quiet (no unusual noises), low vibration opera-
tion. Check that the current draw is within the full load limits as listed on
the rating plate and datasheet.

3.

Refer  to  the  troubleshooting  section  of  these  instructions  if  anything
seems out of the ordinary.

Summary of Contents for TURBO36

Page 1: ...NGLISH US Installation Instructions Operating Instructions ESPAÑOL Instrucciones de instalación Instrucciones de uso Document ID INS00131 A READ AND SAVE THESE INSTRUCTIONS IMPORTANTE LEA ATENTAMENTE ANTES DE USAR ...

Page 2: ...proper use No liability is accepted for damages resulting from improper use 2 Safety Safety messages Your safety and the safety of others are very important Important safety messages are provided in these instructions READ THESE MESSAGES CAREFULLY A safety message alerts you to potential hazards that could hurt you or others Each safety message is preceded by a safety symbol and one of four signal...

Page 3: ...xamples Factories workshops and farms NOTICE This fan is intended for moving air only DANGER Do not use this fan in explosive or potentially explosive at mospheres 3 3 Technical information For detailed technical information please visit our website from which technical datasheets can be viewed and downloaded http productselector vostermans com 4 Installation Before commencing installation 1 Check...

Page 4: ...n according to local regulations NOTICE Overcurrent protection The use of an individual separate overcurrent protective device per fan is highly recommended NOTICE Overload protection The use of an individual separate overload protective device Motor Protective Circuit Breaker per fan is highly recommended 4 2 1 Thermal protection 1 fan motor thermal protection Thermal detectors are built in stand...

Page 5: ...llowing Installation work and electrical wiring must be done by qualified per son s in accordance with all applicable codes and Standards including fire rated construction Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety Standards such a...

Page 6: ...nce subjects Cleaning In areas of application where high levels of contamination are present cleaning intervals should be adjusted accordingly Cleaning is preferably done using a soft brush Do not use any aggressive detergents solvents or chemicals for cleaning Wet cleaning Wet cleaning is allowed using low pressure clean water spray Avoid directing water jets at bearings and electrical connection...

Page 7: ...ce the capacitor Fan rotates in wrong direction 1 fan motors capacitor incorrectly connected Connect according to wiring diagram contact sup plier 3 fan motors supply incorrectly connected Swap any 2 of the 3 phases of the supply Fan speed rpm is too low Supply voltage is too low Check the power supply Incorrect supply frequency Check the power supply Only for 1 fans wrong or defective capacitor R...

Page 8: ...ve atmosphere A mixture of air under atmospheric conditions with flammable sub stances in the form of gases vapours mists or dusts in which after igni tion has occurred combustion spreads to the entire unburned mixture Skilled person Individual with relevant technical education training or experience to en able perceiving risks and avoiding hazards occurring during use of a product ...

Page 9: ...ndebido No se acepta ninguna responsabilidad por los daños que resulten de un uso inadecuado 2 Seguridad Mensajes de seguridad Su seguridad y la de los demás es muy importante En estas instrucciones se incluyen importantes mensajes de seguridad LEA ESTOS MENSAJES ATENTAMENTE Esta información le alerta sobre los peligros potenciales que podrían dañarle a usted o a los demás Cada mensaje de segurida...

Page 10: ... 2 Uso específico El Basket Fan está destinado a crear un movimiento de aire con fines de refrigeración y o ventilación Ejemplos de aplicación Fábricas talleres y granjas AVISO Este ventilador está diseñado para mover aire solamente PELIGRO No utilice este motor en atmósferas explosivas o potencial mente explosivas 3 3 Información técnica Para obtener información técnica detallada visite nuestro s...

Page 11: ...or un electricista calificado Las conexiones eléctricas deben ser hechas de acuerdo con las regulaciones locales Compruebe toda la información en la placa de características y comprobar que este ventilador es adecuado para el suministro eléctrico Para motores de ventiladores 3 comprobar que ESTRELLA DELTA esté correctamente configurado en la regleta de bornes L1 N L2 1 AA US TB L1 L2 L3 3 3 L1 L2 ...

Page 12: ...ncia control frecuencia FC No reduzca la frecuencia a menos del 20 de la frecuencia nominal in dicada en la placa de características Cuando se utiliza un variador de frecuencia las instrucciones de cablea do del fabricante del variador de frecuencia se deben seguir ADVERTENCIA No aumente la frecuencia por encima del valor nominal indica do en la placa de características Control electrónico de la t...

Page 13: ...a funcionar el ventilador cada mes por lo menos 2 horas a toda velocidad para evitar la acumulación de humedad en el motor del ventilador y para mantener el lubricante de los cojinetes en buenas condiciones 7 Mantenimiento PELIGRO Desconectar y aislar completamente el ventilador de la alimen tación eléctrica antes de comenzar el mantenimiento ADVERTENCIA Todos los elementos móviles deben estar com...

Page 14: ...or personas capacitadas Fallo Posible causa Solución posible La vibración excesiva Desequilibrio del hélice hélice dañado Reemplace el hélice Desequilibrio del hélice hélice sucio Limpie el hélice Cojinetes dañados o desgastados Sustituir los cojinetes El ventilador no arranca No hay energía suministrada al ventilador Comprobar todas las fuentes de alimentación Compruebe el fusible disyuntor Si es...

Page 15: ... rango de trabajo Reducir la resistencia del sistema Entrada o salida bloqueada Cojinetes dañados o desgastados Sustituir los cojinetes Las instrucciones detalladas de reparación y reemplazo están disponibles en su proveedor o en Vostermans Ventilation B V Se recomienda encarecidamente utilizar piezas genuinas sólo para el servicio y las reparaciones 9 Fin de vida útil Eliminación Al final de la v...

Page 16: ... IL USA Tel 1 309 827 9798 ventilation vostermansusa com Tmn Klang Jaya Malaysia Tel 60 0 3 3324 3638 ventilation vostermansasia com Shanghai China Tel 86 21 5290 2889 2899 ventilation vostermanschina com 00 0000 is a brand of Vostermans Ventilation B V DocumentID INS00131 A Created 02 03 2021 INS00131 ...

Reviews: