4 | ENGLISH (US)

Original instructions

INS00131-A

Verify that the structure from which the fan is suspended can carry the weight
of the fan.

Make  sure  that  the  fan  is  suspended  rigid  enough,  to  prevent  the  fan  from
swaying or shaking as a result of the forces generated by the fan.

Condensate drain holes

The fan motor has drain holes to allow condensation that may form inside the
motor to leave the motor. After installation, the drain hole at the lowest point
of the motor must be open, the other drain holes must be closed.

Spare  condensate  drain  plugs  are  supplied  with  the  fan.  Keep  all  the  drain
plugs  as  they  must  be  temporarily  reinserted  in  the  open  drain  holes  during
wet cleaning.

Illustration 3: 

Condensate drain plug

WARNING

The fan must be installed with the lowest moving part at least
9ft (2.7m) above floor grade level.

4.2

Electrical

Wiring diagrams

NOTICE

Electrical connection must be carried out by a qualified electri-
cian. Electrical connections must be made in accordance with
local regulations.

Check  the  rating  plate  and  verify  that  this  fan  is  suitable  for  the  available
power supply.

For  3~  fan  motors:  check  that  STAR  /  DELTA  is  properly  configured  on  the
terminal block.

L1

N / L2

1~ 

AA

 US

TB

L1

L2

L3

3~ 

3~ 

L1

L2

L3

AB03 AB04

AB01 AB02

NOTICE!  STAR  is  for  HIGH  voltage  /  DELTA  is  for  LOW
voltage

Control

This fan is supplied without a control or control system. A control or a control
system must be provided for operation of the fan.

Isolator

This fan is supplied without an electrical isolator. An electrical isolator must be
provided to facilitate safe maintenance and troubleshooting.

Grounding

  The  fan  must  be  grounded.  Ground  the  fan  according  to  local

regulations.

NOTICE

Overcurrent protection

The use of an individual separate overcurrent protective device per
fan is highly recommended.

NOTICE

Overload protection

The use of an individual separate overload protective device (Motor
Protective Circuit Breaker) per fan is highly recommended.

4.2.1

Thermal protection

1~ fan motor thermal protection

Thermal  detectors  are  built-in  standard  in  1~  fan  motors.  Thermal  detectors
are  of  the  thermostat  type  TB:  thermostat  opening  on  increase  of
temperature.

In  1~  fan  motors,  the  thermostat  (TB)  is  by  default  wired  in  series  with  the
phase (L) of the supply. The motor is as such self-resetting: when the motor
overheats, the thermostat will switch off the motor automatically and once the
motor has cooled down, the motor will start automatically again.

The  presence  of  the  text  “Thermally  Protected”  on  the  rating  plate  and/or
datasheet indicates that thermal protection is built-in the 1~ fan motor and that
it is wired in series with the phase (L) of the supply.

WARNING

If  the  unexpected  start  of  the  motor  by  the  thermostat  can
cause  a  hazard  or  is  prohibited  by  local  regulations,  the  ther-
mostat must be connected into a control circuit that will not al-
low the motor to restart until the circuit is manually reset.

3~ fan motor thermal protection (optionally available)

Thermal  detectors  are  optionally  available  in  3~  fan  motors.  Thermal
detectors  are  of  the  thermostat  type  TB:  thermostat  opening  on  increase  of
temperature.

In  3~  fan  motors,  the  thermostats  (TB)  are  by  default  wired  to  separate
terminals on the terminal block. An external control circuit can be connected
here. 

NOTICE!  The  thermostats  in  3~  fan  motors  cannot  be

wired in series with the power supply.

Maximum thermostat (TB) load

When connecting an external control circuit to the thermostats, the following
load limits must be observed:

AC

≤ 500 V

Summary of Contents for TURBO36

Page 1: ...NGLISH US Installation Instructions Operating Instructions ESPAÑOL Instrucciones de instalación Instrucciones de uso Document ID INS00131 A READ AND SAVE THESE INSTRUCTIONS IMPORTANTE LEA ATENTAMENTE ANTES DE USAR ...

Page 2: ...proper use No liability is accepted for damages resulting from improper use 2 Safety Safety messages Your safety and the safety of others are very important Important safety messages are provided in these instructions READ THESE MESSAGES CAREFULLY A safety message alerts you to potential hazards that could hurt you or others Each safety message is preceded by a safety symbol and one of four signal...

Page 3: ...xamples Factories workshops and farms NOTICE This fan is intended for moving air only DANGER Do not use this fan in explosive or potentially explosive at mospheres 3 3 Technical information For detailed technical information please visit our website from which technical datasheets can be viewed and downloaded http productselector vostermans com 4 Installation Before commencing installation 1 Check...

Page 4: ...n according to local regulations NOTICE Overcurrent protection The use of an individual separate overcurrent protective device per fan is highly recommended NOTICE Overload protection The use of an individual separate overload protective device Motor Protective Circuit Breaker per fan is highly recommended 4 2 1 Thermal protection 1 fan motor thermal protection Thermal detectors are built in stand...

Page 5: ...llowing Installation work and electrical wiring must be done by qualified per son s in accordance with all applicable codes and Standards including fire rated construction Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety Standards such a...

Page 6: ...nce subjects Cleaning In areas of application where high levels of contamination are present cleaning intervals should be adjusted accordingly Cleaning is preferably done using a soft brush Do not use any aggressive detergents solvents or chemicals for cleaning Wet cleaning Wet cleaning is allowed using low pressure clean water spray Avoid directing water jets at bearings and electrical connection...

Page 7: ...ce the capacitor Fan rotates in wrong direction 1 fan motors capacitor incorrectly connected Connect according to wiring diagram contact sup plier 3 fan motors supply incorrectly connected Swap any 2 of the 3 phases of the supply Fan speed rpm is too low Supply voltage is too low Check the power supply Incorrect supply frequency Check the power supply Only for 1 fans wrong or defective capacitor R...

Page 8: ...ve atmosphere A mixture of air under atmospheric conditions with flammable sub stances in the form of gases vapours mists or dusts in which after igni tion has occurred combustion spreads to the entire unburned mixture Skilled person Individual with relevant technical education training or experience to en able perceiving risks and avoiding hazards occurring during use of a product ...

Page 9: ...ndebido No se acepta ninguna responsabilidad por los daños que resulten de un uso inadecuado 2 Seguridad Mensajes de seguridad Su seguridad y la de los demás es muy importante En estas instrucciones se incluyen importantes mensajes de seguridad LEA ESTOS MENSAJES ATENTAMENTE Esta información le alerta sobre los peligros potenciales que podrían dañarle a usted o a los demás Cada mensaje de segurida...

Page 10: ... 2 Uso específico El Basket Fan está destinado a crear un movimiento de aire con fines de refrigeración y o ventilación Ejemplos de aplicación Fábricas talleres y granjas AVISO Este ventilador está diseñado para mover aire solamente PELIGRO No utilice este motor en atmósferas explosivas o potencial mente explosivas 3 3 Información técnica Para obtener información técnica detallada visite nuestro s...

Page 11: ...or un electricista calificado Las conexiones eléctricas deben ser hechas de acuerdo con las regulaciones locales Compruebe toda la información en la placa de características y comprobar que este ventilador es adecuado para el suministro eléctrico Para motores de ventiladores 3 comprobar que ESTRELLA DELTA esté correctamente configurado en la regleta de bornes L1 N L2 1 AA US TB L1 L2 L3 3 3 L1 L2 ...

Page 12: ...ncia control frecuencia FC No reduzca la frecuencia a menos del 20 de la frecuencia nominal in dicada en la placa de características Cuando se utiliza un variador de frecuencia las instrucciones de cablea do del fabricante del variador de frecuencia se deben seguir ADVERTENCIA No aumente la frecuencia por encima del valor nominal indica do en la placa de características Control electrónico de la t...

Page 13: ...a funcionar el ventilador cada mes por lo menos 2 horas a toda velocidad para evitar la acumulación de humedad en el motor del ventilador y para mantener el lubricante de los cojinetes en buenas condiciones 7 Mantenimiento PELIGRO Desconectar y aislar completamente el ventilador de la alimen tación eléctrica antes de comenzar el mantenimiento ADVERTENCIA Todos los elementos móviles deben estar com...

Page 14: ...or personas capacitadas Fallo Posible causa Solución posible La vibración excesiva Desequilibrio del hélice hélice dañado Reemplace el hélice Desequilibrio del hélice hélice sucio Limpie el hélice Cojinetes dañados o desgastados Sustituir los cojinetes El ventilador no arranca No hay energía suministrada al ventilador Comprobar todas las fuentes de alimentación Compruebe el fusible disyuntor Si es...

Page 15: ... rango de trabajo Reducir la resistencia del sistema Entrada o salida bloqueada Cojinetes dañados o desgastados Sustituir los cojinetes Las instrucciones detalladas de reparación y reemplazo están disponibles en su proveedor o en Vostermans Ventilation B V Se recomienda encarecidamente utilizar piezas genuinas sólo para el servicio y las reparaciones 9 Fin de vida útil Eliminación Al final de la v...

Page 16: ... IL USA Tel 1 309 827 9798 ventilation vostermansusa com Tmn Klang Jaya Malaysia Tel 60 0 3 3324 3638 ventilation vostermansasia com Shanghai China Tel 86 21 5290 2889 2899 ventilation vostermanschina com 00 0000 is a brand of Vostermans Ventilation B V DocumentID INS00131 A Created 02 03 2021 INS00131 ...

Reviews: