6. COMMUNICATIONS
SUPPORTED MODBUS FUNCTIONS
6-11
6.3.7
FUNCTION CODE 08 - LOOPBACK TEST
Modbus Implementation:
Loopback Test
SR469 Implementation:
Loopback Test
This function is used to test the integrity of the communication link. The SR469 will echo the request.
Message Format and Example:
Loopback test from slave 11.
Master Transmission
Bytes
Example (hex)
SLAVE ADDRESS
1
0B
message for slave 11
FUNCTION CODE
1
08
loopback test
DIAG CODE
2
00
must be 00 00
00
DATA
2
00
must be 00 00
00
CRC
2
E0
CRC calculated by the master
A1
Slave Response
SLAVE ADDRESS
1
0B
message from slave 11
FUNCTION CODE
1
08
loopback test
DIAG CODE
2
00
must be 00 00
00
DATA
2
00
must be 00 00
00
CRC
2
E0
CRC calculated by the slave
A1