6. COMMUNICATIONS
MEMORY MAP
6-39
GROUP
ADDR
(hex)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
17D2
RTD #3 Alarm Relays
0
6
1
-
FC113
0
17D3
RTD #3 Alarm Temperature
1
250
1
o
C
F1
130
17D4
RTD #3 Alarm Events
0
1
1
-
FC103
0
17D5
RTD #3 Trip
0
2
1
-
FC115
0
17D6
RTD #3 Trip Voting
1
12
1
-
FC122
3
17D7
RTD #3 Trip Relays
0
3
1
-
FC111
0
17D8
RTD #3 Trip Temperature
1
250
1
o
C
F1
155
17D9
1st and 2nd char. of RTD #3 Name
0
65535
1
-
F22
‘ ‘
...
17DC
7th and 8th char. of RTD #3 Name
0
65535
1
-
F22
‘ ‘
17DD
Reserved
...
17ED
Reserved
17EE
RTD #3 Alarm Temperature (in Fahrenheit)
34
482
1
o
F
F1
266
17EF
RTD #3 Trip Temperature (in Fahrenheit)
34
482
1
o
F
F1
311
RTD #4
17F0
RTD #4 Application
0
4
1
-
FC121
1
17F1
RTD #4 Alarm
0
2
1
-
FC115
0
17F2
RTD #4 Alarm Relays
0
6
1
-
FC113
0
17F3
RTD #4 Alarm Temperature
1
250
1
o
C
F1
130
17F4
RTD #4 Alarm Events
0
1
1
-
FC103
0
17F5
RTD #4 Trip
0
2
1
-
FC115
0
17F6
RTD #4 Trip Voting
1
12
1
-
FC122
4
17F7
RTD #4 Trip Relays
0
3
1
-
FC111
0
17F8
RTD #4 Trip Temperature
1
250
1
o
C
F1
155
17F9
1st and 2nd char. of RTD #4 Name
0
65535
1
-
F22
‘ ‘
...
17FC
7th and 8th char. of RTD #4 Name
0
65535
1
-
F22
‘ ‘
17FD
Reserved
...
180D
Reserved
180E
RTD #4 Alarm Temperature (in Fahrenheit)
34
482
1
o
F
F1
266
180F
RTD #4 Trip Temperature (in Fahrenheit)
34
482
1
o
F
F1
311
RTD #5
1810
RTD #5 Application
0
4
1
-
FC121
1
1811
RTD #5 Alarm
0
2
1
-
FC115
0
1812
RTD #5 Alarm Relays
0
6
1
-
FC113
0
1813
RTD #5 Alarm Temperature
1
250
1
o
C
F1
130
1814
RTD #5 Alarm Events
0
1
1
-
FC103
0
1815
RTD #5 Trip
0
2
1
-
FC115
0
1816
RTD #5 Trip Voting
1
12
1
-
FC122
5
1817
RTD #5 Trip Relays
0
3
1
-
FC111
0
1818
RTD #5 Trip Temperature
1
250
1
o
C
F1
155
1819
1st and 2nd char. of RTD #5 Name
0
65535
1
-
F22
‘ ‘
Summary of Contents for SR469
Page 7: ......
Page 19: ...2 INSTALLATION MECHANICAL 2 5 2 1 5 TERMINAL LOCATIONS Figure 2 11 TERMINAL LAYOUT...
Page 21: ...2 INSTALLATION ELECTRICAL 2 7 Figure 2 12 TYPICAL WIRING DIAGRAM...
Page 32: ...ELECTRICAL 2 INSTALLATION 2 18 2 2 14 TYPICAL 2 SPEED MOTOR WIRING...
Page 39: ...OVERVIEW 3 SR469 OPERATION 3 6 yy SETPOINTS yy S1 SR469 SETUP...
Page 104: ...4 SETPOINT PROGRAMMING S11 MONITORING 4 65 Figure 4 24 TRIP COIL SUPERVISION...
Page 113: ...S12 ANALOG I O 4 SETPOINT PROGRAMMING 4 74...
Page 244: ...8 469PC PROGRAM WAVEFORM CAPTURE 8 13 Figure 8 11 WAVEFORM CAPTURE...