HARDWARE FUNCTIONAL TESTING
7. TESTING
7-2
7.2 HARDWARE FUNCTIONAL TESTING
7.2.1
PHASE CURRENT ACCURACY TEST
The SR469 specification for phase current accuracy is
±
0.5% of 2xCT when the injected current is < 2xCT. Perform the steps below to verify
accuracy.
1.
Alter the following setpoint:
SETPOINT S2:SYSTEM SETUP\CURRENT SENSING\PHASE CT PRIMARY: 1000A
2.
Measured values should be
±
10A. Inject the values shown in the table below and verify accuracy of the measured values. View the
measured values in:
ACTUAL VALUES A2:\METERING DATA\CURRENT METERING
Table 7-1 PHASE CURRENT TEST
INJECTED
CURRENT
1 A UNIT
(A)
INJECTED
CURRENT
5 A UNIT
(A)
EXPECTED
CURRENT
READING
(A)
MEASURED
CURRENT
PHASE A
(A)
MEASURED
CURRENT
PHASE B
(A)
MEASURED
CURRENT
PHASE C
(A)
0.1
0.5
100
0.2
1.0
200
0.5
2.5
500
1
5
1000
1.5
7.5
1500
2
10
2000
7.2.2
VOLTAGE INPUT ACCURACY TEST
The SR469 specification for voltage input accuracy is
±
0.5% of full scale(273V). Perform the steps below to verify accuracy.
1.
Alter the following setpoints:
SETPOINT S2:SYSTEM SETUP\VOLTAGE SENSING\VT CONNECTION TYPE: Wye
SETPOINT S2:SYSTEM SETUP\VOLTAGE SENSING\VOLTAGE TRANSFORMER RATIO: 10.00:1
2.
Measured values should be
±
13.65V. Apply the voltage values shown in the table and verify accuracy of the measured values. View the
measured values in:
3.
ACTUAL VALUES A2:\METERING DATA\VOLTAGE METERING
Table 7-2 VOLTAGE INPUT TEST
APPLIED
LINE-NEUTRAL
VOLTAGE
(V)
EXPECTED
VOLTAGE
READING
(V)
MEASURED
VOLTAGE
A-N
(V)
MEASURED
VOLTAGE
B-N
(V)
MEASURED
VOLTAGE
C-N
(V)
30
300
50
500
100
1000
150
1500
200
2000
270
2700
Summary of Contents for SR469
Page 7: ......
Page 19: ...2 INSTALLATION MECHANICAL 2 5 2 1 5 TERMINAL LOCATIONS Figure 2 11 TERMINAL LAYOUT...
Page 21: ...2 INSTALLATION ELECTRICAL 2 7 Figure 2 12 TYPICAL WIRING DIAGRAM...
Page 32: ...ELECTRICAL 2 INSTALLATION 2 18 2 2 14 TYPICAL 2 SPEED MOTOR WIRING...
Page 39: ...OVERVIEW 3 SR469 OPERATION 3 6 yy SETPOINTS yy S1 SR469 SETUP...
Page 104: ...4 SETPOINT PROGRAMMING S11 MONITORING 4 65 Figure 4 24 TRIP COIL SUPERVISION...
Page 113: ...S12 ANALOG I O 4 SETPOINT PROGRAMMING 4 74...
Page 244: ...8 469PC PROGRAM WAVEFORM CAPTURE 8 13 Figure 8 11 WAVEFORM CAPTURE...