1.5kVA / 2.0kVA EDP Double Conversion UPS Specifications
:
Parameter
Specifications
Notes
Dimensions
17.25” x 5.250” x 13.625”
WxHxD
Operating Temperature
-34°C to +74°C
-29°F to 165°F
Humidity
5 to 95%
Non-Condensing
Cooling System
Forced Air Cooling
AC Input
AC Circuit Breaker Rating
20Amps
Connections
4 Position Terminal Block
Phase
Single Phase 3-wire
Voltage
120V Nominal
55V to 155V Load Dependant
See AC Output Current Capacity
Frequency
60Hz Nominal
40-120Hz Operating Range
Line Voltage Acceptance Thresholds
145V when Line greater than 155V
108V at 70% or greater Load
96V at 69% or less Load
±2%
Low Line Voltage Thresholds
80V at 70% or greater Load
68V at 69% or less Load
55V at 40% or less Load
±2%
Power Requirements
1.36kVA
1.8kVA
Max. Capacity during Recharging
Input Power Factor
≥ 0.95
At Rated Output, when Input Waveform
Distortion is <1%
AC Output
Output Power Connection
4 Position Terminal Block
Voltage
120VAC
Voltage Regulation
2%
Rated Frequency
60Hz
Frequency Regulation
5%
Current Capacity
8.75A at
Nominal Voltage
11.67A at
Nominal Voltage
70% or less to achieve 96V of Input V
40% or less to achieve 55V of Input V
Efficiency
> 85% Line Mode at 100% Load
Approx. 83% Inverter Mode
Voltage Waveform
Sine Wave
Distortion Factor of Voltage Waveform
Linear load: 3% or less,
100% rectifier load: 7% or less
At Rated Output
Transient
Voltage
Variation
Rapid Load Change
Rated Voltage ±5%
0% ↔ 100% at
Transient or Output Switch
Recovery
At Rated Output
Rapid Input
Voltage Change
±10% Variation
Response Time
2 Cycles or less
Load Power Factor
0.7
Variation Range 0.7 to 1.0
Over Current Protection
Auto-Switch to Bypass Circuit at 105%
Load or more
Automatic Recovery
Overload Capability
Inverter
105%
Bypass
200%
800%
Battery Input
Fuse
100A
Connection
Anderson Powerpole 75
Battery Type
12V Sealed Lead Acid Battery
Rated Capacity
100Ahr
60Ahr
Quantity
3
4
Connected in Series
Backup Time
Load Dependant
Generated Heat
200W
250W
Input Leakage Current
3mA or less
Acoustic Noise
≤ 40dB
≤ 45dB
Alarm & Timer Relay Contacts
Switching Power
60W, 62.5VA
Minimum Contact Rating:
10mVDC
, 10μA
Switching Voltage
220VDC, 250VAC
Switching Current
2.0A
Carrying Current
2.0A