MD-1000I / MD-2000I / MD-3000I
UPS Installation and Hook-Up
6.3
Equipment Connection Sequence
Connect the UPS to source of power, but make sure the power source and
the UPS are both reliably shut down.
Before connecting equipment to the UPS outlet, you must perform the ini-
tial configuration.
Connect the equipment to the UPS, making sure that all the equipment is
turned off.
6.3.1
EPO connection configuration
Function
Connection wire gauge
Suggested gauge
EPO
4 - 0.32 mm
2
(12 - 22 AWG )
0.82 mm
2
(18 AWG)
MD Series
63
Leave the EPO plug installed on the UPS' EPO port, even if you don't plan to
use the EPO function.
Fig. 6-3 - 1 EPO plug
Follow the instructions for the EPO port as stated in
Chapter 3.2.5 EPO port.