PAGE 22 — DAC7000 SERIES GENERATORS• OPERATION AND PARTS MANUAL — REV. #0 (02/15/16)
Single Phase Load — 60 Hz
Always be sure to check the nameplate on the generators
and equipment to insure the wattage, amperage and
frequency requirements are satisfactorily supplied by the
generators for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require
130—150% more wattage than the rating on the nameplate,
as the wattage is influenced by the efficiency, power factor
and starting system of the equipment.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generators is 1.0 See Table 3 below
when connecting loads.
NOTICE
If wattage is not given on the equipment's name plate,
approximate wattage may be determined by multiplying
nameplate voltage by the nameplate amperage
Table 3. Power Factor By Load
Type Of Load
Power Factor
Single-phase induction motors
0.4 - 0.75
Electric heaters, incandescent
lamps
1.0
Fluorescent lamps, mercury
lamps
0.4 - 0.9
Electronic devices,
communication equipment
1.0
Common power tools
0.8
NOTICE
When using a combination of dual receptacles, total
load should not exceed the rated capacity of the
generator.
NOTICE
When connecting power tools or equipment pay close
attention to the required starting current capacity.
LOAD APPLICATIONS
To determine the running wattage for your load, multiply the
running wattage as indicated by steps 1, 2, and 3 below:
1. INCANDESCENT LOADS
Lights, heaters and similar appliances.
total the running wattage and multiply by 1.
Example:
29 light bulbs @ 100W each = 2.9 kW
use a 3 kW generator.
2. SMALL MOTORS
Drills and other small power tools.
Total the running wattage and multiply by 2.
Example:
A 1 inch drill runs at 1 kW
use a 2 kW generator
3. LARGE MOTORS
Submersible pumps, table saws etc.
Total the running wattage and multiply by 3.
Example:
A conveyor belt runs at 8 kW
use a 24 kW generator.
Extension Cables
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used.
Cables should be sized to allow for
distance in length and amperage so that the voltage
drop between the generators and point of use (load)
is held to a minimum
. Use the cable selection chart (Table 4)
as a guide for selecting proper cable size.
NOTICE
Motors and motor-driven equipment draw much greater
current for starting than during operation. Always use
an adequate size extension cable which can carry the
required load.
NOTICE
The idle control device is operated at a minimum load
capacity of 100W. If the load capacity is less than 100W,
place the idle control switch in the
OFF
position.
Summary of Contents for DAC7000SS
Page 15: ...DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 PAGE 15 NOTE...
Page 59: ...DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 PAGE 59 NOTES...
Page 64: ...PAGE 64 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 GENERATOR ASSY...
Page 66: ...PAGE 66 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 CONTROL PANEL ASSY...
Page 74: ...PAGE 74 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 BATTERY ASSY...
Page 76: ...PAGE 76 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 MUFFLER ASSY...
Page 78: ...PAGE 78 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 FUEL TANK ASSY...
Page 82: ...PAGE 82 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 ENCLOSURE ASSY...
Page 86: ...PAGE 86 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 RUBBER SEALS ASSY...
Page 171: ...DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 PAGE 171 NOTES...