DAC7000 SERIES GENERATORS • OPERATION AND PARTS MANUAL — REV. #0 (02/15/16) — PAGE 29
OPERATION
4. If the engine does not start within 10 seconds after the
key is turned to the
START
position, wait for about 30
seconds and repeat the procedure as described in
step 4. above.
5. When the engine starts, the oil pressure light and
charge light should go out. If these lights stay on,
immediately stop the engine and check the system and
wiring (refer to the Engine Operation Manual).
6. Let the engine idle for five minutes with the
Idle Control
Switch
(Figure 19) placed in the
ON
position.
Figure 19. Idle Control Switch (ON)
Output Voltage Verification
1. Place
main
circuit breaker (Figure 20) in the
ON
position.
Figure 20. Main Circuit Breaker (ON)
NOTICE
Placing the idle control switch (Figure 19) in the
OFF
position allows the engine to operate at a maximum
speed of about 3600 RPM's.
When the idle control switch is placed in the up position
(
ON
), the generator will run at idle speed (2200 RPM's)
until a load is applied, at that time the engine speed
will increase to 3600 RPM's as long as a load is being
applied.
When the load is not in use, the engine speed will drop
back to the idle mode after about 3 seconds.
ON
ON
25A
25A
2. Place
GFCI
circuit breaker (Figure 21) in the
ON
position.
Figure 21. GFCI Circuit Breaker (ON)
3. Read voltmeter on front panel of generator (Figure 22)
and verify that 120 VAC is displayed. Using an external
voltmeter as shown in Figure 22, verify that 120 VAC
is present at the 120V twist-lock and GFCI duplex
receptacles.
Figure 22. 120V GFCI/L5-30R Receptacles
NOTICE
When using a combination of dual receptacles, total
load should not exceed the rated capacity of the
generator.
Summary of Contents for DAC7000SS
Page 15: ...DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 PAGE 15 NOTE...
Page 59: ...DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 PAGE 59 NOTES...
Page 64: ...PAGE 64 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 GENERATOR ASSY...
Page 66: ...PAGE 66 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 CONTROL PANEL ASSY...
Page 74: ...PAGE 74 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 BATTERY ASSY...
Page 76: ...PAGE 76 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 MUFFLER ASSY...
Page 78: ...PAGE 78 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 FUEL TANK ASSY...
Page 82: ...PAGE 82 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 ENCLOSURE ASSY...
Page 86: ...PAGE 86 DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 RUBBER SEALS ASSY...
Page 171: ...DAC7000 SERIES GENERATORS OPERATION AND PARTS MANUAL REV 0 02 15 16 PAGE 171 NOTES...