DCa125USI3CaN 60 hz geNerator • operatIoN aND partS maNUal — rev. #2 (09/24/13) — page 23
OUtPUt tErMINAL PANEL fAMILIArIzAtION
120 VAC GFCI Receptacles
There are two 120 VAC, 20 amp GFCI (Duplex Nema
5-20R) receptacles provided on the output terminal panel.
These receptacles can be accessed in
any voltage
selector switch
position. Each receptacle is protected by a
20 amp circuit breaker. These breakers are located directly
above the GFCI receptacles. Remember the load output
(current) of both GFCI receptacles is dependent on the load
requirements of the U, V, and W output terminal lugs.
Pressing the
reset
button resets the GFCI receptacle after
being tripped. Pressing the
test button
(Figure 7) in the
center of the receptacle will check the GFCI function. Both
receptacles should be tested at least once a month.
Figure 7. G.F.C.I. Receptacle
Twist Lock Dual Voltage 120/240 VAC Receptacles
There are three 120/240V, 50 amp auxiliary twist-lock (CS-
6369) receptacles (Figure 8) provided on the output
terminal panel. These receptacles can
only
be accessed
when the voltage selector switch is placed in the
single-
phase 240/120 position.
Figure 8. 120/240V Twist-Lock
Auxiliary Receptacles
Each auxiliary receptacle is protected by a 50 amp circuit
breaker. These breakers are located directly above the
GFCI receptacles. Remember the load output (current) on
all three receptacles is dependent on the load requirements
of the
output terminal lugs
.
Turn the
voltage regulator control knob
(Figure 9) on the
control panel to obtain the desired voltage. Turning the knob
clockwise will
increase
the voltage, turning the knob
counter-clockwise will
decrease
the voltage.
Figure 9. Voltage Regulator Control Knob
Removing the Plastic Face Plate (Hard Wire Hookup
Panel)
The
output terminal lugs
are protected by a plastic face
plate cover (Figure 10). Unscrew the securing bolts and
lift the plastic terminal cover to gain access to the terminal
enclosure.
After the load wires have been securely attached to the
terminal lugs, reinstall the plastic face plate.
Figure 10. Plastic Face Plate
(Output Terminal Lugs)
Summary of Contents for DCA125USI3CAN
Page 19: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 19 Notes...
Page 51: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 51 Notes...
Page 54: ...page 54 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 GENERATOR ASSY...
Page 70: ...page 70 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 BATTERY ASSY...
Page 72: ...page 72 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 Muffler Assy...
Page 74: ...page 74 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 FUEL TANK ASSY...
Page 91: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 91 notes...