page 26 — DCa125USI3CaN 60 hz geNerator • operatIoN aND partS maNUal — rev. #2 (09/24/13)
gENErAtOr OUtPUtS
geNerator oUtpUt voltageS
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the
voltage selector
switch
(Figure 13). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the
voltage regulator
(VR)
control
knob
located on the control panel.
Voltage Selector Switch
The voltage selector switch (Figure 13) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 13. Voltage Selector Switch
Voltage Selector Switch Locking Button
To lock the voltage selector switch,
press and hold the
red button
located at the bottom of the switch. While
holding the red button down, insert a pad lock into the hole
next to the button to retain it in the inward locked position.
When the lock is removed, the red button is spring loaded
and will return to its normal outward unlocked position.
CAUTION
Never
change the position of the
voltage selector
switch
while the engine is running.
alWaYS
place
circuit breaker in the
OFF
position before selecting
voltage
.
table 7. voltages available
UvWo output
terminal lugs
voltage Selector Switch
3-phase 240/139v position
voltage Selector Switch
3-phase 480/270v position
3Ø
line-line
208V
220V
240V
416V
440V
480V
1Ø
line-Neutral
120V
127V
139V
240V
254V
277V
voltage Selector Switch Single-phase 240/120v position
1Ø
line-Neutral/
line-line
120V
Line-Neutral
N/A
N/A
240V
Line-Line
N/A
N/A
Generator Amperage
Table 8 shows the
maximum
amps the generator can
provide.
DO NOT
exceed the maximum amps as listed..
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Table 9 and Table 10 show what amount of current is
available at the GFCI receptacles when the output terminals
and twist lock receptacles are in use. Be careful that your
load does not to exceed the available current capability at
the receptacles.
table 8. generator maximum amps
rated voltage
maximum amps
1Ø 120 Volt
277.8 amps (4 wire)
301A x 2 (Zigzag)
1Ø 240 Volt
138.9 amps (4 wire)
301A (Zigzag)
3Ø 240 Volt
301 amps
3Ø 480 Volt
150 amps
table 9. 1Ø gFCI receptacle load Capacity
KW in use
twist lock (C6369)
available load
Current (amps)
1Ø 240/120V
GFCI Duplex
5-20R 120V
72.0
0 amps/receptacle
70.8
5 amps/receptacle
69.6
10 amps/receptacle
68.4
15 amps/receptacle
67.2
20 amps/receptacle
table 10.
3Ø
gFCI receptacle load Capacity
Kva in Use
(UvWo terminals)
available load
Current (amps)
3Ø 240/480V
GFCI Duplex
5-20R 120V
125
0 amps/receptacle
121
5 amps/receptacle
117
10 amps/receptacle
113
15 amps/receptacle
108
20 amps/receptacle
Summary of Contents for DCA125USI3CAN
Page 19: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 19 Notes...
Page 51: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 51 Notes...
Page 54: ...page 54 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 GENERATOR ASSY...
Page 70: ...page 70 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 BATTERY ASSY...
Page 72: ...page 72 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 Muffler Assy...
Page 74: ...page 74 DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 FUEL TANK ASSY...
Page 91: ...DCA125USI3CAN 60 hz Generator operation and parts manual rev 2 09 24 13 page 91 notes...