SG1400/1600C4F STUDIO GENERATOR • OPERATION MANUAL — REV. #0 (07/22/20) — PAGE 25
CAMLOK/VOLTAGE OUTPUT PANEL
The definitions below describe the controls and functions
of the Camlok/Voltage Output Panel (Figure 8).
1.
Legacy Paralleling Receptacle
— This 20-pin
receptacle allows legacy parallelling capability via
Intelligen Controllers.
2.
Paralleling Cable In/Out Receptacles
— These
communication connection ports are used when
multiple generators are going to be connected.
3.
CB8/CB9 Circuit Breakers
— These circuit breakers
protect the 125/250 VAC CS6369 auxiliary output
receptacles from overload.
4.
Auxiliary CS6369 Output Receptacles
— These
auxiliary twist-lock receptacles provide 250/120 VAC@
50-amps. These receptacles can
only
be accessed
when the voltage selector switch is placed in the
single-phase 240/120V
position
5.
Generator Voltage Test Points
— To determine if
the generator's output voltage is present and correct,
connect a test meter to these test points during
troubleshooting and maintenance.
6.
Camlok Receptacles
— These output voltage
connection points (6 pairs) are used for load connection.
ALWAYS
pay close attention when connecting and
disconnecting power cables from these camlok
receptacles.
The possibility exists of electrocution,
shock or even death if cables are connected or
unplugged when the bus hot indicator lamp is lit.
NOTICE
The Camlok/Voltage Output Panel is available in many
configurations. Figure 8 represents the most commonly
used panels.
7.
Bates 120VAC Output Receptacles
— These
receptacles provide AC voltage output. Each receptacle
is protected by a 100 amp breaker. These receptacles
cannot be used when the voltage selector switch is in
the 3
Ø
277/480 VAC position.
8.
120 VAC Output Receptacles
— These 15-amp
receptacles provide 120 VAC output. The maximum
allowable combined amps (both receptacles) is 25 amps
when the voltage selector switch in the 3
Ø
277/480 VAC
position.
9.
BUS Hot Indicator Lamp
— When lit, this indicator
lamp informs that the voltage bus is active (high
voltage).
NEVER
connect or disconnect cables from
the camlok or auxiliary receptacles when this indicator
is
ON
. The possibility exists of electrocution, shock or
even death if cables are connected or unplugged when
this indicator is lamp lit.
10.
CB4/CB5 Circuit Breakers
— These circuit breakers
protect the 120 VAC auxiliary output receptacles from
overload.
11.
CB6/CB7 Circuit Breakers
— These circuit breakers
protect the bates output receptacles from overload.