PAGE 26 — SG1400/1600C4F STUDIO GENERATOR • OPERATION MANUAL — REV. #0 (07/22/20)
CIRCUIT BREAKER PANEL
The definitions below describe the controls and functions
of the Main Breaker Panel (Figure 9).
1.
CB3 Circuit Breaker
— This breaker monitors,
senses the voltage bus. If breaker trips, signal is sent
to controller.
2.
CB2 Circuit Breaker
— This breaker monitors, senses
the generator voltage bus. If breaker trips, signal is
sent to controller.
3.
Main Circuit Breaker
— This 600 amp breaker
protects the camlok receptacles (load) from overload.
4.
Electronic Trip Unit
— This unit protects the generator
from in-rush current (load spikes).
NOTICE
When setting the trip point on the electric trip unit, be
careful not to set the trip point too high. Setting the
trip point too high may cause the main breaker not
to trip. This condition could cause serious damage to
the equipment, and serious bodily harm even death to
operating personnel.
Always be conservative when setting the trip point. The
trip setting for this generator is position B 600 amps.
DO NOT
adjust the trip point setting when the
equipment is in operation.
Electronic Trip Unit
Instantaneous Trip Setting - Amps
Push to Trip
Test
Status
A — 500
B — 600
C — 800
D — 1000
E — 1250
F — 1500
G — 2000
H — 2500
E
D
C
B
A
H
G
F
450 AMP
LONG — INST.
Electronic Trip Unit
Instantaneous Trip Setting - Amps
Push to Trip
Test
Status
A — 500
B — 600
C — 800
D — 1000
E — 1250
F — 1500
G — 2000
H — 2500
E
D
C
B
A
H
G
F
450 AMP
LONG — INST.
2
3
4
1
Figure 9. Main Breaker Panel