SG1400/1600C4F STUDIO GENERATOR • OPERATION MANUAL — REV. #0 (07/22/20) — PAGE 35
STARTUP
BEFORE STARTING
1. Place the Control Power switch (Figure 21) on the
digital control panel in the up position (ON).
Figure 21. Control Power Switch (ON)
2. Place the voltage selector switch (Figure 22) in the
desired voltage setting position. The corresponding
Voltage Status LED on the control panel will light to
indicate the selected voltage (Figure 23).
Figure 22. Voltage Selector Switch
120/208 3Ø Position
Figure 23. Voltage Status LEDs
CAUTION
The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation
when operating.
ON
(UP)
120/208
3Ø
120/240
1Ø
277/480
3Ø
120/208
3Ø
277/480
3Ø
120/208
3Ø
120/240
1Ø
277/480 VAC 3 PHASE
LIGHTS
IF SELECTED
120/208 VAC 3 PHASE
120/240 VAC 1 PHASE
3. Verify that all three circuit breakers (Figure 24) are in
the
ON
position prior to starting the engine.
Figure 24. Circuit Breakers (ON)
4. If unit is to be used in parallel with another unit,
interconnect the units. Interconnect the output buses
with suitable power cables to carry full load capacity.
Special male-to-male Camlok cables will be needed.
For 480 V mode, it is recommended that one 4/0 cable
per phase, neutral and ground be used. For 208V
mode, use two 4/0 cables per phase and neutral and
one 4/0 cable for ground. Also connect the parallel
communication cables.
5. Connect the load to the receptacles on the Camlok/
Voltage Output Panel. When the camloks are inserted
into the outlet connector, rotate clockwise until they are
locked in place. Make sure the camloks are connected
securely.
6. Press the
MODE
button (Figure 25) on the Digital
Controller Display and select manual mode (MAN)
with the arrow keys. Press
ENTER
key when MAN is
highlighted on the screen.
NOTICE
If it is necessary to prime engine before starting (such
as after changing a fuel filter or running out of fuel),
please reference the maintenance section in this
manual "Priming The Engine".
Electronic Trip Unit
Instantaneous Trip Setting - Amps
Push to Trip
Test
Status
A — 500
B — 600
C — 800
D — 1000
E — 1250
F — 1500
G — 2000
H — 2500
E
D
C
B
A
H
G
F
450 AMP
LONG — INST.
ON
VERIFY CIRCUIT BREAKERS ARE
ON