dca220sscu/4i 60 hz generaTor• operaTion manual — rev. #0 (10/25/12) — page 27
OUtpUt terMiNaL paNeL CONNeCtiONs
3Ø-480v uvWo Terminal output voltages
1. Jumper the voltage change-over board for 480V
operation as shown in Figure 23. This configuration
uses 6 jumper plates in 3 different positions. Remember
there are 2 jumper plates at every position. Every
jumper plate
must
be used.
Figure 23. Voltage Change-Over Board 480V
Configuration
2. Connect the load wires to the UVWO terminals as
shown in Figure 24.
Figure 24. UVWO Terminal Lugs 3Ø-480V
Connections
NOTICE
alWaYs
make sure that the connections to the UVWO
terminals are
secure
and
tight
. The possibility of arcing
exists, that could cause a fire.
1Ø-480v uvWo Terminal output voltages
1. Make sure the voltage change-over board is jumpered
for 480V operation as shown in Figure 23.
2. Connect the load wires to the UVWO terminals as
shown in Figure 25.
Figure 25. UVWO Terminal Lugs 1Ø-480V
Connections
1Ø-277v uvWo Terminal output voltages
1. Make sure the voltage change-over board is jumpered
for 480V operation as shown in Figure 23.
2. Connect the load wires to the UVWO terminals as
shown in Figure 26.
Figure 26. UVWO Terminal Lugs 1Ø-277V
Connections
Summary of Contents for MQ Power Whisperwatt DCA220SSCU
Page 5: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 5 notes...
Page 51: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 51 notes...
Page 54: ...page 54 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 GENERATOR ASSY...
Page 70: ...page 70 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 battery ASSY...
Page 72: ...page 72 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 muffler ASSY...
Page 74: ...page 74 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 fuel tank ASSY...
Page 76: ...page 76 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 ENCLOSURE ASSY...
Page 89: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 89 notes...