page 34 — dca220sscu/4i 60 hz generaTor • operaTion and parTs manual — rev. #0 (10/25/12)
GeNeratOr start-Up prOCeDUre (aUtO MODe)
sTarTing (auTo mode)
danger
Before connecting this generator to any
building’s electrical system, a
licensed
electrician
must install an
isolation
(transfer) switch.
Serious damage to
the building’s electrical system may occur
without this transfer switch.
cauTion
When connecting the generator to a isolation (transfer)
switch,
alWaYs
have power applied to the generator’s
internal battery charger. This will ensure that the engine
will not fail due to a dead battery.
Warning
When running the generator in the
auTo
mode,
remember the generator can start up at any time without
warning.
never
attempt to perform any maintenance
when the generator is in the auto mode.
cauTion
The engine speed switch
must
be set to the “High”
position when running in the
auto-start
mode. Failing
to set the switch in the proper position can result in
damage to your generator when it turns on.
NOTICE
When the generator is set in the
auTo
mode, the
generator will
automatically start
in the event of
commercial power falling below a prescribed level
by means of a contact closure that is generated
automatically by a transfer switch.
NOTICE
When the
Auto Off/Reset Manual
switch is placed
in the
auTo
position, the engine glow plugs will be
warmed and the engine will start automatically.
When starting generator in
auTo
mode use the “Manual
Start-up” procedure except where noted (see below).
1. Perform steps 1 through 5 in the Before Starting section
as outlined in the Manual Starting Procedure.
2. Place the
engine speed switch
(Figure 49) in the
high
position
Figure 49. Engine Speed Switch (High)
3. Place the
auto off/reset manual switch
(Figure 50)
in the
auTo
position.
Figure 50.
auto off/reset manual
Switch (AUTO)
4. Continue operating the generator as outlined in the
Manual Start-up procedure (start at step 5).
Summary of Contents for MQ Power Whisperwatt DCA220SSCU
Page 5: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 5 notes...
Page 51: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 51 notes...
Page 54: ...page 54 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 GENERATOR ASSY...
Page 70: ...page 70 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 battery ASSY...
Page 72: ...page 72 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 muffler ASSY...
Page 74: ...page 74 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 fuel tank ASSY...
Page 76: ...page 76 dca220sscu 4i 60 hz generator operation and Parts manual rev 0 10 25 12 ENCLOSURE ASSY...
Page 89: ...DCA220ssCU 4i 60 hz generator operation manual rev 0 10 25 12 page 89 notes...