PAGE 54 — DCA-100SSJU — PARTS AND OPERATION MANUAL (STD) — REV. #2 (05/03/01)
DCA-100SSJU — MAINTENANCE
Cleaning the Fuel Strainer
Clean the fuel strainer if it contains dust or water. Remove
dust or water in the strainer cap and wash it in diesel. Securely
fasten the fuel strainer cap so that fuel will not leak. Check
the fuel strainer every 200 hours of operation or once a month.
Check Oil Level
Check the crankcase oil level prior to each use, or when the
fuel tank is filled. Insufficient oil may cause severe damage
to the engine. Make sure the generator is level. The oil level
must be between the two notches on the dipstick as shown
in page 27, Figure 9.
Generator Storage
For storage of the generator for over 30 days, the following
is required:
"
Drain the fuel tank completely.
"
Completely drain the oil from the crankcase and refill
with fresh oil.
"
Clean all external parts of the generator with a cloth.
"
Cover the generating set and store in a clean, dry place.
General Inspection
Prior to each use, the generating set should be cleaned and
inspected for deficiencies. Check for loose, missing or
damaged nuts, bolts or other fasteners. Also check for fuel
or oil leaks.
Engine Side, Fuel, Oil and Coolant (Refer to the Engine
Instruction Manual)
Air Cleaner
Every 50 hours: Remove air cleaner element and clean heavy
duty paper element with kerosene, or foam element with
liquid detergent and hot water. Wrap foam element in a cloth
and squeeze dry. For heavy duty paper element, wipe
excess kerosene with towel
Fuel Addition
Add diesel fuel (the grade may vary according to season
and locations). Always pour through the mesh filter.
Removing Water from the Tank
After prolonged use, water and other impurities accumulate
in the bottom of the tank. Occasionally remove the drain
cock and drain the contents. During cold weather, the greater
the empty volume inside the tank, the easier it is for water
to condense. This can be reduced by always keeping the
tank as full as possible.
Air Removal
If air enters the fuel injection system of a diesel engine,
starting becomes impossible. After running out of fuel, or
after disassembling the fuel system, bleed the system
according to the following procedure.
To restart after running out of fuel, turn the key switch to the
“START” position for 15-30 seconds. Try again, if needed.
This unit is equipped with an automatic air bleeding system.
Service Daily
If engine is operating in very dusty and dry grass conditions,
a clogged air cleaner will result in high fuel consumption,
loss of power and excessive carbon buildup in the
combustion chamber.
Summary of Contents for Power WHISPERWATT DCA-100SSJU
Page 2: ...PAGE 2 DCA 100SSJU PARTS AND OPERATION MANUAL STD REV 2 05 03 01...
Page 22: ...PAGE 22 DCA 100SSJU PARTS AND OPERATION MANUAL STD REV 2 05 03 01 DCA 100SSJU GENERATOR DECALS...
Page 27: ...DCA 100SSJU PARTS AND OPERATION MANUAL STD REV 2 05 03 01 PAGE 27 NOTE PAGE...
Page 91: ...DCA 100SSJU PARTS AND OPERATION MANUAL STD REV 2 05 03 01 PAGE 91 NOTE PAGE...