PAGE 42 — DCA-220SSJ/SSJU — OPERATION AND PARTS MANUAL — REV. #0 (02/04/14)
Figure 14. Connecting Loads
Connecting Loads
Loads can be connected to the generator by the
Ouput
Terminal Lugs
or the convienience receptacles (Figure 14).
Make sure to read the operation manual before attempting
to connect a load to the generator.
To protect the output terminals from overload, a
3-pole, 600A
main
circuit breaker is provided. Make sure to
switch
ALL
circuit breakers to the
OFF
position prior to
starting the engine.
DCA-220SSJ/SSJU — OUTPUT TERMINAL PANEL FAMILIARIZATION
Over Current Relay
An
over current relay
(Figure 15) is connected to the main
circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the
reset button
on the over cur-
rent relay must be pressed. The over current relay is lo-
cated in the control box.
Figure 15. Over Current Relay