DCA-400SSK — PARTS AND OPERATION MANUAL (STD)— REV. #3 (09/17/01) — PAGE 39
480 Volt Set position
The voltage change-over board 480V set position uses all
6 plates in 3 different connection places. There are 2
plates at every position (Every plate is used). See figure
23 below.
FIGURE 23. Voltage Change-over Board 480V set position.
3 Phase, 480 Volt
The following connection, with the voltage change-over
board set into the 480V set position (See Figure 23), can
offer
THREE PHASE
power at 480V. After hooking up the
hard wires to the lugs as shown in figure 24 below, 480V
will be the voltage output.
Single Phase, 480 Volt
The following connection, with the voltage change-over
board set into the 480V set position (See Figure 23), can
offer
SINGLE PHASE
power at 480V. After hooking up
the hard wires to the lugs as shown in figure 25 below,
480V will be the voltage output.
FIGURE 24. Hard Wire Hookup for Three Phase 480V
FIGURE 26. Hard Wire Hookup for Single Phase 277V
FIGURE 25. Hard Wire Hookup for Single Phase 480V
Single Phase, 277 Volt
The following connection, with the voltage change-over
board set into the 480V set position (See Figure 23), can
offer
SINGLE PHASE
power at 277V. After hooking up
the hard wires to the lugs as shown in figure 26 below,
277V will be the voltage output.
DCA-400SSK — OUTPUT TERMINAL PANEL OVERVIEW
Summary of Contents for Power WHISPERWATT DCA-400SSK
Page 2: ...PAGE 2 DCA 400SSK PARTS AND OPERATION MANUAL STD REV 3 09 17 01...
Page 27: ...DCA 400SSK PARTS AND OPERATION MANUAL STD REV 3 09 17 01 PAGE 27 NOTE PAGE...
Page 53: ...DCA 400SSK PARTS AND OPERATION MANUAL STD REV 3 09 17 01 PAGE 53 NOTE PAGE...
Page 59: ...DCA 400SSK PARTS AND OPERATION MANUAL STD REV 3 09 17 01 PAGE 59 NOTE PAGE...
Page 104: ...PAGE 104 DCA 400SSK PARTS AND OPERATION MANUAL STD REV 3 09 17 01 DCA 400SSK RUBBER SEAL ASSY...
Page 113: ...DCA 400SSK PARTS AND OPERATION MANUAL STD REV 3 09 17 01 PAGE 113 NOTE PAGE...